7
2. PROPER CHIMNEY HEIGHT:
The chimney shall terminate at least 3 feet above the highest point where it passes through the roof of a
building and at least 2 feet higher than any portion of a building within a horizontal distance of 10 feet.
(See Fig. 2a).
Fig. 2: Proper chimney termination height for pitched roofs
If the chimney penetrates a roof more than 10 feet from a ridge, wall or parapet, a minimum of 3 feet
above roof or exit point must be maintained. See Figure 2b.
If the roof is flat rather than the normal residential pitched roof, refer to Figure 3 for proper clearances.
Fig. 3: Proper chimney termination height for flat roofs
3. PROPER VENT CONNECTOR PIPE/CHIMNEY CONNECTION:
The vent connector pipe should extend only to (and not beyond) the inside wall of the chimney (See Fig.
4). A thimble should be used to connect the vent connector pipe to the chimney so that the vent
connector pipe may be readily removed in case of inspection or replacement.
Fig. 4: Proper insertion of the vent connector in the chimney.
Summary of Contents for VCH8FA119P60B
Page 4: ...2...
Page 34: ...32 V Sequence of Operations Flow Chart...
Page 35: ...33...
Page 36: ...34 VI Trouble Shooting Flow Chart...
Page 37: ...35...
Page 38: ...36...
Page 39: ...37...
Page 40: ...38...
Page 42: ...40 Appendix A Replacement Parts for VCH8FA119...
Page 43: ...41...
Page 44: ...42 Appendix B VCH8FA119P60 PSC Wiring Diagram...