Use the following procedure for initial start-up of the boiler:
1) Verify
that the venting, water piping, gas piping and electrical system are installed properly.
2)
Confirm all electrical, water and gas supplies are turned off at the source and that vent is clear of obstructions.
3)
Confirm that all manual shut-off gas valves between the boiler and gas source are closed.
4)
If not already done, flush the system to remove sediment, flux, and traces of boiler additives.
5) Fill the boiler and hydronic system with water meeting the following requirements below (also see the NOTICE on the
next page):
• pH between 6.5 and 9.5
• Hardness less than 7 grains/gallon
• Chlorides less than 200 ppm
• Iron level less than 0.5 ppm
• Copper level less than 0.1 ppm
• Pressurize the system to at least 14.5 psi at the boiler
6) Bleed air from the heat exchanger and piping system.
7)
Check all gas piping for leaks and purge piping sections that are filled with air. Refer to the
National Fuel Gas Code
for
additional information on testing and purging gas lines.
8)
Confirm vent system is complete and free of obstructions before attempting to fire boiler.
9) Inspect all wiring for loose, uninsulated or miswired connections.
10) If the boiler is to be converted to LP Gas (propane), convert as described in Appendix A. If boiler is operating at
elevations above 4,500 ft., see Appendix B of this manual for setup instructions.
XI. Start-Up and Checkout
WARNING
Burn Hazard. The maximum operating pressure of this boiler is 30 psig (210 kPa) or 80 psig (340 kPa),
depending on the model and safety relief valve option selected. Never exceed the maximum allowable
working pressure on the heat exchanger ASME plate.
DANGER
Explosion Hazard. Do not use matches, candles, open flames or other ignition source to check for
leaks.
Make sure that the area around the boiler is clear and free from combustible materials, gasoline and
other flammable vapors and liquids.
WARNING
Completely read, understand and follow all instructions in this manual before attempting start-up.
NOTICE
Safe lighting and other performance criteria were met with the gas train assembly provided on the boiler
when the boiler underwent the test specified in ANSI Z21.13.
Summary of Contents for Raptor RPTR085
Page 1: ...1...
Page 13: ...13 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued...
Page 87: ...87 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued...
Page 88: ...88 X Wiring continued...
Page 97: ...97 Operating Instructions XI Start Up and Checkout continued...
Page 142: ...142 XV Repair Parts continued 3A 3B 3C 3D 3F 3E 3G 3H 3O 3P 3Q 3R 3J 3K 3I 3M 3N 3L All Models...
Page 148: ...148 XV Repair Parts continued 6D 6B 6A 6E 6I 6G 6L 6N 6H 6C 6K 6M 6C 6C 6J 6J 6F All Models...
Page 172: ...172...