THE INDICATOR LIGHTS UP:
The
solenoid valve is closed and the
plumbing leak test is carried out.
The indicator does not light up if the
solenoid valve is open.
MAXIMUM TIME = longest allowed time
for continuous flow.
Resets every time the
tap closes for a minimum of three seconds
(3s). If the set time is exceeded the water
is cut off and the alarm needs to be reset-
ted. The maximum time setting prevents
serious water damage in cases when a
seal breaks, the tap has been left open or
the toilet bowl leaks. The water flows only
for the time set with the maximum time
setting.
RESET BUTTON’S
functions:
1. Resetting the water guard.
2. Resetting an exceeded maximum
time (the light blinks together with
the maximum time light).
3. Resetting the alarm caused by the
leakage sensor attached to the
extension unit. (Slowly blinking
light – – –).
4. Resetting the alarm caused by lost
connection to the solenoid valve
(fast blinking light ---).
TIME EXTENSION
extends the maximum
time of continuous water flow. This
function is useful e.g. when watering
your lawn, filling the pool or washing
your car. The Veimart unit shuts off the
water supply when the maximum time
+ extended time is over and the water
is still running (requires a reset). The
setting automatically resets.
IN AWAY MODE the flow of water has
been completely stopped.
The red indi-
cator is lit. Reset the Veimart unit back
to basic (home) mode by pressing the
Away button again. The indicator light
goes off. The water guard is also on in
the Away mode: If there is a leak in the
plumbing (even though the water mains
has been shut off) there will be no water
before you press the reset button.
THE BLUE LIGHT
is always on
when
the flow sensor detects that water is
flowing in the piping. This means that
the solenoid valve is open. If the flow
is very low, the blue indicator will not
light up and the leakage sensor will
cut off the water supply.
TIP!
The maximum time
also leads to more
economical water
consumption. Using
too much hot water in
particular can be
expensive.
NOTE!
See our FAQ on our
website to find answers
to frequently asked
questions
www.v
eimart.
fi/en/f
aq
WITH THE TEST BUTTON
you
can override the 10 minute
forced control delay and shut the
solenoid valve for a dripping test:
1. Close all taps.
2. Press the test button. This
causes the solenoid valve to
close (an indicator illuminates
above the test button).
3. Open the tap just a little and
see whether the Veimart unit
stops the water flowing after
a while.
4. Stop the test by pushing the
reset button.
NOTE!
The solenoid valve
stays
open for 10 more minutes after
the Veimart unit no longer
detects water flowing (when the
blue indicator light goes off).
This means that the device does
not require a reset if the tap is
dripping for a few minutes by
accident.
VEIMART INSTRUCTIONS FOR USE
THANK YOU FOR CHOOSING THE VEIMART WATER GUARD!
It is extremely easy to use the Veimart water guard. After the simple initial setup, the device is always on. If the tap water plumbing of
your house works as it should (no leakage, normal pressure, over 3.5 bar), the Veimart system runs automatically so that you don’t have
to pay any attention to it. The device monitors the condition of the plumbing and cuts off the water supply if it detects a leak or if the
water is left running for too long.
WHAT TO DO IF THE WATER IS NOT FLOWING
(the water guard has been triggered): Find out if a tap is dripping enough for
the Veimart unit to have interpreted it as a leak so that it has stopped the water. Press the reset button and water will flow
normally. If you can’t find out why the water guard was triggered, see if it happens again after the alarm was resetted. Typically
leaks occur on seals, taps and toilet bowls. The Veimart unit also recognizes dripping leaks if the water is not used for a few hours.
The smaller the leak, the longer it takes to detect it.
For example one drop every minute is enough to trigger the water guard over-
night. If it is not possible to find the leak with the naked eye, a professional may be able to find the leak with pressure test equipment.
www.veimart.fi/en
Visuad032018
Veimart Oy
| VAT number: 2712062-7 | Takatie 6 90440 KEMPELE | Customer s358 44 244 0140 | [email protected]