52
AC310 Universal AC Drive Service Manual
3.9 OH Fault Detection and Maintenance
1. GND1 as a reference ground, measuring HEAT, the normal voltage is 0.5V-1V. If the HEAT
voltage is abnormal, the power board voltage detection circuit is abnormal, test the power
board voltage detection circuit.
2. HEAT -IN abnormal voltage, for the control board input circuit module temperature
collection failure, replace the corresponding resistors: R86, R87, R88, R89, or capacitors C9,
C10.
Summary of Contents for AC310
Page 23: ...22 AC310 Universal AC Drive Service Manual 2 7 Switching Power Supply...
Page 47: ...46 AC310 Universal AC Drive Service Manual 3 7 Keyboard Circuitry...
Page 54: ...53 AC310 Universal AC Drive Service Manual 3 10 Current Acquisition Detection and Maintenance...
Page 55: ...54 AC310 Universal AC Drive Service Manual 3 11 OC Fault Detection and Maintenance...