AC310 Universal AC Drive Service Manual
10
Black pen
U
0
V0
W0
N
N
N
AC file
8
-
9
V
8-9V
8-9V
8-9V
8-9V
8-9V
Single measurement
measurement
measurement
measurement
measurement
8
.
0
2
V
8.03V
8.01V
8.20V
8.20V
8.20V
When the drive voltage is at a positive value, the drive is turned on, and at a negative
value, the drive is turned off, so use the AC gear to measure it.
◼
Measurement of normal voltage points during operation:
Red pen
UTP
VTP
VTP
Black pen
U0
V0
W0
DC grade
16V
16V
16V
The UTP, VTP, and WTP voltages are generated by the VDR, if there is a problem there,
the drive voltage generated by the switching power supply is faulty Problems.
Measure the voltage of the drive signal on the control board when it is not in operation
(DC phase).
UH
UL
VH
VL
WH
WL
GND
5V
5V
5V
5V
5V
5V
Waveforms of one of the drive signals and GND outputs during operation: as follows
(if the output waveforms are abnormal, the control board is abnormal)
Measure the voltage of each drive signal and GND is about 11.5v when running with
ACgear.
◼
Use two ripple probes (pay attention to isolation) to connect to the upper and lower arm
drivers of the same phase (directly soldered to the IGBT pins), power up and run the
whole machine, and test the driving waveforms. (If there is no waveform, the module
may be damaged, or the UH, UL, VH, VL, WH, WL provided on the control board may
be defective.).
Summary of Contents for AC310
Page 23: ...22 AC310 Universal AC Drive Service Manual 2 7 Switching Power Supply...
Page 47: ...46 AC310 Universal AC Drive Service Manual 3 7 Keyboard Circuitry...
Page 54: ...53 AC310 Universal AC Drive Service Manual 3 10 Current Acquisition Detection and Maintenance...
Page 55: ...54 AC310 Universal AC Drive Service Manual 3 11 OC Fault Detection and Maintenance...