Chapter 6: Overhaul and Maintenance 

During frequency inverter normal operation, except for daily inspections, periodic (such as machine 

overhaul or inspections at least every six months as required) inspections must be performed according 

to the following table, to preven t trouble before it happens. 

Inspectio

n period   

Inspecti

on part 

Inspection 

items 

Inspection content   

Inspection 

methods 

Criteria 

At any 

time 

Display   

LED 

display 

If display is abnormal or 

not?   

Vision 

No abnormal 

At any 

time 

Cooling 

system   

Fan   

If there is abnormal 
vibration or abnormal 
noise. 

Visual 
examination 

and listening 

No abnormal 

At any 

time 

Noume

non 

Surroundi
ng 
environm
ent

 

 

Temperature

humidity

dust

harmful gas 

Visual 
examination 

  smelling

feeling 

By 2-1 term 

At any 

time 

Input 

terminal 

Voltage 

If input, output voltage is 

abnormal 

Detect R

S

and U

V

terminal 

according to the 

standards 
regulation 

periodic   

Main 

circuit 

panorama 

If the fastener loosen , 

whether having the hot 

shot trail , whether 

having discharging or 

not phenomenon , dust 

are too much, if the 

wind way is blocked up   

Visual,

tighten

clean 

No abnormal 

Electrolitic 

capacitor 

If surface is abnormal   

Visual 

No abnormal 

Wire 

conductiv

e bar 

Whether loosen   

Visual 

No abnormal 

Terminal 

Whether the bolt or 

screw loosen 

tighten 

No abnormal 

During the examination, not allowed to dismantle or rock a component for no reason, even pull off a 

connector assembly. Otherwise, it can not run or enter malfunction display state. And it will bring faults 

of  the  component,even  damage  the  host  switch  component  IGBT  module.  When  needing 

measurement, user should pay attention to various different meters which may reach very different 

measurement results. Pointer voltmeter is recommended to use to measure input voltage. Rectifier 

voltmeter is recommended to use to measure output voltage. Pliers galvanometer is recommended to 

use to measure input and output current. And electrodynamics wattmeter is recommended to use to 

measure power. 

Summary of Contents for AC70E-S2-1R5G

Page 1: ...messages of installing wiring keyboard operation simple function table troubleshooting maintenance only For parameters setting detail pls read AC70 general used series manual or consult us For the bes...

Page 2: ...anger If not abide the regulations or requirements in this manual there is danger of body injuryeven death and machinesystemdamage Do not wire while the power is conneted Otherwise there is danger of...

Page 3: ...e is ok pls open it and check the inverter If damage caused in transport it is not duty of Veich company But please contact Veich or the transport company immediately After checking the product please...

Page 4: ...age compensation function if motor rated voltage is 100 the voltage can be set in the 50 100 scope the voltage output should not exceed the input voltage AVR adjust When the grid voltage fluctuates ch...

Page 5: ...and avoid the impact of electromagnetic interference Ensure all equipments connected to frequency inverter are connected to star earth or common earth bus by short and thick cable as well as frequenc...

Page 6: ...c condition of safe and reliable running of the product For right earthing please read the following notice carefully In order to avoid electric shock earthing cable should be the size as electric equ...

Page 7: ...e without metal dust oil water or etc into inverter please do not install inverter on flammable material such as food and etc Place without radioactive material or flammablematerial Place without pois...

Page 8: ...inverter cooling please follow installation conditions as below It should adopts hanging style or closet style with upright installation and keeps enough space with surroundings or the wall Multi inve...

Page 9: ...inverter and keyboard W1 H 1 W H D D1 MODEL WW W1 H H1 D D1 INSTALLATION APERTURE AC70E S2 R40G 88 75 142 5 129 5 142 132 5 AC70E S2 R75G AC70E S2 1R5G AC70E T3 R75G AC70E T3 1R5G AC70E S2 2R2G 106 90...

Page 10: ...to obey aimed to ensuring safe use best performance and reliable running Note Analog monitor output is special output of meters such as frequcy meter current meter voltage meter and etc It can not be...

Page 11: ...0 75 kW 200 120W 100 1 5 kW 400 300W 100 1 5 kW 100 300W 100 2 2 kW 250 400W 100 2 2 kW 75 300W 100 3 7 kW 150 500W 100 Main circuit terminals Terminal Name Function definition Braking resistance ter...

Page 12: ...amme set definition Pls refer F 01 F 04 X2 Multi function contact input X2 X3 Multi function contact input X3 X4 Multi function contact input X4 AO Analog output Physical type of output signal 0 10V 0...

Page 13: ...oring state While given frequency or PID or given torque are set by keyboard Shift key Select digit of function no modified by up down key Select parameter digits modified by up dowm key Change LED mo...

Page 14: ...ator and the A indicator light at the same time display value is the motor speed Flashing When the A indicator and the V indicator flashing at the same time display value is gived PID value On When th...

Page 15: ...tting range and definition Factary default pr op ert y Refer to page Comm unicati on code E 00 Control method selection 0 Open loop vector controlwithout PG 1 V F control mode 1 69 100H E 01 Running c...

Page 16: ...Both channel is valid if non zero value main channelpriority 3 Main channel K auxiliary channel 4 main channel K auxiliary channel 5 MAX main channel K auxiliary channel 6 MIN main channel K auxiliar...

Page 17: ...elerate decelerate time datum point 0 Motor rated frequency 1 Maximum frequency LED hundreds digit Equidistance stop function 0 Disable 1 Enable LEDThousands digit reserve 0000 74 10FH E 16 Frequencyg...

Page 18: ...shock is enabled 1010 77 115H E 22 V F slip compensation 0 200 100 78 116H E 23 Energy saving mode selection LED unitdigit Auto energy saving selection 0 disable 1 enable LED tens digit V F slip compe...

Page 19: ...ng starting frequency when stop 0 00 60 00Hz 0 00Hz 81 125H E 38 DC braking time when start 0 0 10 0s 0 0s 81 126H E 39 Jump frequency 1 0 00 600 0Hz Fmax 0 00Hz 81 127H E 40 Jump frequency 2 0 00 600...

Page 20: ...tage suppression threshold voltage 105 160 135 86 135H E 54 Ratio of dynamicbraking 0 100 80 86 136H E 55 DC bus under voltage protecting value 60 90 65 86 137H E 56 Reserve 86 138H E 57 Reserve 86 13...

Page 21: ...ent in deceleration suppression 0 Disable 1 Enable 2 Enable frequency reducing for protecting over current 0001 91 143H External terminal parameters Code funcion Fucntion name Setting range and define...

Page 22: ...2 18 Frequency main channel selection terminal3 19 Frequency main channel selection terminal4 20 Program running pause 21 Program restart 22 Timer trigger terminal 23 Timer reset terminal 24 Counter r...

Page 23: ...ute UP DW adjusting LED hundred digit STOP RESE of keypad effective range selection 0 STOP RESE key valid only when under keypad control 1 STOP RESE key valid underany run command source LED thousand...

Page 24: ...educing acceleration time 0 1 6500 0s 1 0s 97 217H F 24 Acceleration time 2 0 1 6500 0s 98 218H F 25 Deceleration time 2 98 219H F 26 Acceleration time 3 98 21AH F 27 Deceleration time 3 98 21BH F 28...

Page 25: ...inal input voltage lower limit 0 00V F 42 0 50V 101 229H F 42 VS1 terminal input voltage upper limit F 41 10 00V 9 50V 101 22AH F 43 VS1 terminal input voltage gain 0 01 5 00 1 00 101 22BH F 44 VS2 te...

Page 26: ...0 Positive characteristic 1 Negative characteristic LED ten digit AS input characteristic selection 0 Positive characteristic 1 Negative characteristic LED hundred digit VS2 input characteristic sele...

Page 27: ...5 00 1 00 106 245H F 70 UP DW terminalpreset frequency 0 00Hz upper limit freqeuncy 0 00Hz 106 246H F 71 UP DW Power off memorized frequency 0 00Hz upper limit freqeuncy 0 00Hz 106 247H Special functi...

Page 28: ...20 Integral time constant I 0 1 100 0s 2 0s 109 314H H 21 Differentialgain D 0 0 10 0 0 0 109 315H H 22 Sampling period 0 01 60 00s 0 10s 110 316H H 23 PID controldeviation limit 0 0 20 0 0 0 110 317...

Page 29: ...step speed direction and accel decel time 4 113 327H H 40 6 step speed direction and accel decel time 5 113 328H H 41 7 step speed direction and accel decel time 6 113 329H H 42 8 step speed directio...

Page 30: ...rate 0 1200bps 1 2400bps 2 4800bps 3 9600bps 4 19200bps 5 38400bps 3 116 345H H 70 Communication setting frequency ratio 0 00 20 00 1 00 116 346H H 71 Time of communication time out 0 0 6500 0s 10 0s...

Page 31: ...tionover limit Prolong Deceleration time Reduce load inertiaor improve inverter capacitanceor add braking unit Detectpowervoltage and clear fault E oU3 Constant speedover volt age Power voltage fluctu...

Page 32: ...isdamaged Electromagneticdisturb Prolong acceleration time Checkperipheryequipments and restart afrer fault cleared Seeksupport from factory Check system wiring earth shield and dealas required E oH...

Page 33: ...age Check keyboard wire Seeksupport from factory E CPE Parameter copy fault Parameter copy communication is fault Copy keyboard is not match the inverter Check wire Select the specified external keybo...

Page 34: ...n periodic Main circuit panorama If the fastener loosen whether having the hot shot trail whether having discharging or not phenomenon dust are too much if the wind way is blocked up Visual tighten cl...

Page 35: ...volt megger measures the frequency inverter Its insulation resistance should not smaller than 4M When using the general ohmmeters to measure current the current in the input end will has imbalance ph...

Page 36: ...being authorized by our company When quality problem appears our company only undertakes three guarantee service as the 11 1 and 11 2 responsibilities above If user needs more responsibility guarantee...

Page 37: ...tive C07H C 8 PID feedback quantitative C08H C 9 Module temperature C09H C 10 Accumulative operation time hour C0AH C 11 Accumulative operation time after latest power on Min C0BH C 12 Output current...

Page 38: ...input terminal on off state X1 terminal stage X3 terminal stage X4 terminal stage Output terminal connect disconnect state schematic diagram Reserve Reserve Reserve Reserve Y2 terminal stage Y1 termi...

Page 39: ...ault Units E07H Er 08 Running direction while the latest fault 0 Forward 1 reverse E08H Er 09 Running status while the latest fault 0 close down 1 stable speed 2 acceleration 3 deceleration E09H Er 10...

Reviews: