ment
.
A
false echo storage detects and marks these false
echoes
,
so that they are no longer taken into account for the
level measurement
.
A
false echo memory should be created
with empty vessel so that all potential interfering re
fl
ections will
be detected
.
G
ating out of false signals
C
hange now
?
P
roceed as follows
:
1
M
ove from the measured value display to the main menu
by pushing
[
OK
]
.
2
S
elect the menu item
"
S
ervice
"
with
[-
>
]
and con
fi
rm with
[
OK
]
.
N
ow the menu item
"
F
alse signal suppression
"
is
displayed
.
3
C
on
fi
rm
"
F
alse signal suppression
-
C
hange now
"
with
[
OK
]
and select in the below menu
"
C
reate new
"
.
E
nter the
actual distance from the sensor to the product surface
.
A
ll
false signals in this area are detected by the sensor and
saved after con
fi
rming with
[
OK
]
.
N
ote
:
C
heck the distance to the product surface
,
because if an
incorrect
(
too large
)
value is entered
,
the existing level will be
saved as false signal
.
T
he
fi
lling level would then no longer be
detectable in this area
.
T
his function enables reading out parameter adjustment data
as well as writing parameter adjustment data into the sensor
via the indicating and adjustment module
.
A
description of the
function is available in the operating instructions manual
"
I
ndicating and adjustment module
"
.
T
he following data are read out or written with this function
:
l
M
easured value presentation
l
A
djustment
l
M
edium
l
V
essel form
l
D
amping
l
L
inearisation curve
l
S
ensor
-
TAG
l
D
isplayed value
l
D
isplay unit
l
S
caling
C
opy sensor data
S
et up with the indicating and adjustment module
PLICSCOM
VEGASON
63
-
4
...
20
m
A
/
HART
35
28777
-
EN
-