5 Set up with the display and adjustment module PLICSCOM

VEGASON 62 • Foundation Fieldbus

51862-EN-210616

100%

0%

0,25 

m

(9.8

4")

m

(196.

9")

2

1

3

Fig. 7: Parameterisation example, Min./max. adjustment
1  Min. level = max. distance (depending on the sensor)

2  Max. level = min. distance (final value of the dead zone, depending on the 

sensor)

3  Reference plane

The actual product level during this adjustment is not important, 

because the min./max. adjustment is always carried out without 

changing the product level. These settings can be made ahead of 

time without the instrument having to be installed.

High nozzles or vessel installations, such as e. g. struts or agitators as 

well as buildup and weld joints on the vessel walls, cause interfering 

reflections which can impair the measurement. A false echo storage 

detects and marks these false echoes, so that they are no longer 

taken into account for the level measurement. A false echo memory 

should be created with low level so that all potential interfering reflec

-

tions will be detected.

False signal suppression

Change now?

Proceed as follows:
1.  Move from the measured value display to the main menu by 

pushing 

[OK]

2.  Select the menu item " 

Service

" with 

[->]

 and confirm with 

[OK]

Now the menu item " 

False signal suppression

" is displayed. 

3.  Confirm " 

False signal suppression - Change now

" with 

[OK]

 and 

select in the below menu " 

Create new

". Enter the actual distance 

from the sensor to the medium surface. All false signals in this 

area are detected by the sensor and saved after confirming with 

[OK]

Service - False signal 

suppression

Summary of Contents for VEGASON 62

Page 1: ...Quick setup guide Ultrasonic sensor for continuous level measurement VEGASON 62 Foundation Fieldbus Document ID 51862...

Page 2: ...ay and adjustment module PLICSCOM 9 5 1 Insert display and adjustment module 9 5 2 Setup steps 9 5 3 Menu schematic 12 6 Set up with smartphone tablet PC notebook via Bluetooth 14 6 1 Preparations 14...

Page 3: ...lying with all prevailing regulations and directives The instrument must only be operated in a technically flawless and reliable condition The operator is responsi ble for the trouble free operation o...

Page 4: ...lt information from measuring transduc ers NE 53 Compatibility of field devices and display adjustment components For further information see www namur de 1 7 Environmental instructions Protection of...

Page 5: ...rovals process seal process temperature signal output voltage supply protection protection class Data matrix code for VEGA Tools app SIL identification with SIL rating ex works Move to www vega com an...

Page 6: ...the so called dead zone in which measurement is not possible is maintained The exact value of the dead zone is stated in chapter Technical data 1 2 Fig 1 Minimum distance to the max level 1 blocking d...

Page 7: ...sor through the cable entry 6 Lift the opening levers of the terminals with a screwdriver see following illustration 7 Insert the wire ends into the open terminals according to the wir ing plan Fig 3...

Page 8: ...2 Wiring plan single chamber housing I2C Display 1 1 2 5 6 7 8 Fig 4 Wiring plan single chamber housing 1 Voltage supply signal output 4 3 Wiring plan double chamber housing I2C 1 1 2 Fig 5 Wiring pla...

Page 9: ...ositions in 90 offset can be selected and turn to the right until it clicks into place 3 Screw housing lid with inspection window tightly back on Disassembly is carried out in reverse order The displa...

Page 10: ...ica tion for example Aqueous solution Medium Liquid 4 Select in the menu item Application the vessel the application and the vessel form for example Storage tank Vessel shape Storage tank The sensor m...

Page 11: ...nd weld joints on the vessel walls cause interfering reflections which can impair the measurement A false echo storage detects and marks these false echoes so that they are no longer taken into accoun...

Page 12: ...is area 5 3 Menu schematic Information Depending on the version and application the highlighted menu windows may not always be available Basic adjustment Basic adjustment 1 Display Diagnostics Service...

Page 13: ...c adjustment 4 Display Diagnostics Service Info False signal suppression 4 1 Change now Extended setting 4 2 Fast level change 1 m min Simulation 4 3 Start simulation Reset 4 4 Reset now Unit of measu...

Page 14: ...ooth 1 Switch On Bluetooth active Off Bluetooth not active The security concept of Bluetooth operation absolutely requires that the default setting of the sensor PIN be changed This prevents unau thor...

Page 15: ...IN is still effective Note Bluetooth access can only be established if the current sensor PIN differs from the default setting 0000 It is possible both when the PIN is deactivated and when it is activ...

Page 16: ...sage Con necting is displayed For the first connection the operating device and the sensor must authenticate each other After successful authentication the next con nection functions without authentic...

Page 17: ...able Measured variable distance between lower edge of the transducer and medium surface Measuring range Liquids up to 8 m 26 25 ft Bulk solids up to 3 5 m 11 48 ft Dead zone 0 4 m 1 312 ft Electromech...

Page 18: ...18 Notes VEGASON 62 Foundation Fieldbus 51862 EN 210616...

Page 19: ...19 Notes VEGASON 62 Foundation Fieldbus 51862 EN 210616...

Page 20: ...ing scope of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change withou...

Reviews: