7 Diagnosis, asset management and service
VEGAPULS WL 61 • Profibus PA
38062-EN-140801
Code
Text mes-
sage
Cause
Rectification
PA DevS-
pec
Diagnosis
F125
Imper-
missible
electronics
tempera-
ture
– Temperature of the
electronics in the non-
specified section
– Check ambient tem-
perature
– Isolate electronics
– Use instrument with
higher temperature
range
Bit 8
F260
Error in the
calibration
– Error in the calibra-
tion carried out in the
factory
– Error in the EEPROM
– Exchanging the elec-
tronics
– Send instrument for
repair
Bit 9
F261
Error in the
configura-
tion
– Error during setup
– False signal suppres-
sion faulty
– Error when carrying
out a reset
– Repeat setup
– Repeat reset
Bit 10
F264
Installa-
tion/Setup
error
– Adjustment not within
the vessel height/
measuring range
– Max. measuring range
of the instrument not
sufficient
– Check or correct
installation and/or
parameter adjustment
– Use an instrument
with bigger measuring
range
Bit 11
F265
Meas-
urement
function
disturbed
– Sensor no longer
carries out a measure-
ment
– Operating voltage
too low
– Check operating
voltage
– Carry out a reset
– Disconnect operating
voltage briefly
Bit 12
The following table shows the error codes and text messages in the
status message "
Function check
" and provides information on causes
as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
C700
Simulation ac-
tive
– A simulation is active
– Finish simulation
– Wait for the automatic end
after 60 mins.
The following table shows the error codes and text messages in the
status message "
Out of specification
" and provides information on
causes as well as corrective measures.
Function check
Out of specification