36
6 Set up with the display and adjustment module PLICSCOM
VEGAPULS 66 • 4 … 20 mA/HART - two-wire
28438-EN-170927
If a linearisation curve is selected, the measuring signal is no longer
necessarily linear to the filling height. This must be considered by the
user especially when setting the switching point on the limit signal
transmitter.
In this menu item you can enter an unambiguous designation for the
sensor, e.g. the measurement loop name or the tank or product des-
ignation. In digital systems and in the documentation of larger plants,
a singular designation should be entered for exact identification of
individual measuring points.
Sensor-TAG
Sensor
With this menu item, the Basic adjustment is finished and you can
now jump to the main menu with the
[ESC]
key.
In the menu item "
Display
" you can define how the measured value
should be presented on the display.
The following indication values are available:
•
Height
•
Distance
•
Current
•
Scaled
•
Percent
•
Lin. percent
The selection "
scaled
" opens the menu items "
Display unit
" and
"
Scaling
". In "
Display unit
" there are the following options:
•
Height
•
Ground
•
Flow
•
Volume
•
Without unit
Depending on selection, the different units are in turn available.
In the menu item "
Scaling
", the requested numerical value with deci-
mal point is entered for 0 % and 100 % of the measured value.
There is the following relationship between the indication value in the
menu "
Display
" and the adjustment unit in the menu "
Device settings
":
•
Indication value "
Distance
": Presentation of the measured value in
the selected adjustment unit, e.g. m(d).
Displayed value
Scaled
▼
Basic adjustment - Sen-
sor TAG
Display - Indicated value