11 Diagnostics and servicing
VEGAMET 342 • 4 … 20 mA
63731-EN-221107
Error code
Cause
Rectification
F040
General hard-
ware error
Hardware error
Switch the instrument off and on
Carry out a reset
Send instrument for repair
Error code
Cause
Rectification
S016
Adjustment:
Min./Max. ex-
changed
The min./max.
adjustment
points were ex-
changed.
Carry out the adjustment again, correct
the min. and max. values.
S017
Adjustment:
Span too small
Adjustment span
too small
Carry out a fresh adjustment and in-
crease the distance between min./max.
adjustment
S021
Scaling: Span
too small
Scaling span too
small
Carry out a fresh scaling, increase the
distance between min./max. scaling.
S022
Scaling: Scaling
value too large
Value for one
of the two scal-
ing points is too
large
Carry out the scaling again, correct the
min. and max. values.
S062
Pulse priority too
small
Pulse priority too
small
Increase under "
Output
" the entry "
Pulse output all
" so that max. one pulse
per second is output.
S104
Measurement
loop deactivated
The measuring
point is deacti-
vated
Activate measuring point
S110
Relay: Span too
small
Relay switching
points too close
together
Increase the difference between the two
relay switching points
S111
Relay: Switching
points inter-
changed
Relay switching
points inter-
changed
Change relay switching points for "
On/
Off
"
S115
Pump control:
Faulty interfer-
ence behaviour
Several relays
are assignef to
the pump control
which are not set
to the same fail-
ure mode
All relays which are assigned to the
pump control must be set to the same
failure mode
S116
Pump control:
Operating mode
faulty
Several relays
that are not con-
figured with the
same mode are
assigned to the
pump control
All relays which are assigned to the
pump control must be set to the same
mode