32
5 Connecting to power supply
VEGAFLEX 86 • 4 … 20 mA/HART - two-wire
49477-EN-150102
5.7 Wiring plan - version IP 66/IP 68, 1 bar
1
2
Fig. 25: Wire assignment in permanently connected connection cable
1 brown (+) and blue (-) to power supply or to the processing system
2 Shielding
5.8 Supplementary electronics
To make a second measured value available for use, you can use the
supplementary electronics - additional current output.
Both current outputs are passive and need a power supply.
1
2
+
( )
(-)
I
4...20mA
I I
4...20mA
7
8
+
( )
(-)
3
1
2
Fig. 26: Terminal compartment, double chamber housing, supplementary elec
-
tronics - additional current output
1 First current output (I) - Voltage supply and signal output (HART)
2 Second current output (II) - Voltage supply and signal output (without HART)
3 Ground terminal for connection of the cable screen
The radio module PLICSMOBILE is an external GSM/GPRS radio
unit for transmission of measured values and for remote parameter
adjustment.
Wire assignment, con-
nection cable
Supplementary electron-
ics - Additional current
output
Supplementary elec-
tronics - Radio module
PLICSMOBILE