N
ote
:
T
he menu items used for the adjustment are also used for entering the
scaling data
.
W
e thus recommend writing down the scaling data for
plant documentation or for a possible later correction of the adjust
-
ment
.
7
.
3
C
orrect sensor adjustment
F
or a correction of the sensor adjustment
,
the
HART
communication
must be again activated
.
T
his is carried out in the menu
"
M
easure
-
ment
"
,
menu item
"
U
nit
"
.
E
nter here the unit in which the adjustment
was carried out
.
T
he
HART
communication is now started again
.
T
he
VEGADIS
62
is
again
S
econdary
M
aster for the sensor and loads the adjustment data
from the sensor
.
T
hen enter the modi
fi
ed values for the
"
M
easuring range begin
"
and
"
M
easuring range end
"
.
T
he entered value for the measuring range begin and end are
transferred to the sensor when saving
.
P
roceed as previously described for a new indication scaling
.
7
.
4
PACT
ware
/
DTM
and
PLICSCOM
W
ith an existing
HART
connection from
VEGADIS
62
to the sensor
,
adjustment changes in the sensor can also be carried out via other
adjustment systems such as
PACT
ware
/
DTM
or
PLICSCOM
.
T
his
does not cause con
fl
icts
,
but the changes are not updated automati
-
cally in
VEGADIS
62
.
F
or updating
,
a
HART
connection is required
.
T
o
do this
,
the signal circuit must be interrupted and then re
-
connected
.
A
s an alternative
,
it is possible to set the unit in the menu
"
M
easurement
"
brie
fl
y to
"
USER
"
.
I
f it is then again reset to a unit
supported by the sensor such as for example
"
bar
"
or
"
m
"
,
the changes
carried out in the meantime via other adjustment systems are updated
in the
VEGADIS
62
.
VEGADIS
62
37
7
S
et up sensors
36469
-
EN
-
120329