Quick setup guide
Differential pressure transmitter with
metallic measuring cell
VEGADIF 85
Profibus PA
Document ID: 53575
Page 1: ...Quick setup guide Differential pressure transmitter with metallic measuring cell VEGADIF 85 Profibus PA Document ID 53575...
Page 2: ...t display and adjustment module 10 5 2 Parameter adjustment Quick setup 11 5 3 Parameter adjustment Extended adjustment 15 5 4 Menu overview 15 6 Set up with smartphone tablet PC notebook via Bluetoot...
Page 3: ...ns This is a state of the art instrument complying with all prevailing regulations and directives The instrument must only be operated in a technically flawless and reliable condition The operating co...
Page 4: ...r fault information from measuring transduc ers NE 53 Compatibility of field devices and display adjustment components NE 107 Self monitoring and diagnosis of field devices For further information see...
Page 5: ...nical data Serial number of the instrument QR code for device identification Numerical code for Bluetooth access optional Manufacturer information To find order data documents or software related to y...
Page 6: ...he medium Abrasion and mechanical influences Protect your instrument against moisture ingress through the following measures Use a suitable connection cable see chapter Connecting to power supply Tigh...
Page 7: ...el single chamber precision casting 2 Aluminium single chamber 3 Stainless steel single chamber electropolished 4 Plastic double chamber 5 Aluminium stainless steel double chamber housing precision ca...
Page 8: ...of the cable gland and remove blind plug 4 Remove approx 10 cm 4 in of the cable mantle strip approx 1 cm 0 4 in of insulation from the ends of the individual wires 5 Insert the cable into the sensor...
Page 9: ...connection compartment single chamber housing 1 Voltage supply signal output 2 For display and adjustment module or interface adapter 3 Selection switch for instrument address 4 For external display a...
Page 10: ...90 It is not necessary to interrupt the power supply Proceed as follows 1 Unscrew the housing lid 2 Place the display and adjustment module on the electronics in the desired position and turn it to t...
Page 11: ...y adapt the sensor to the application select the menu item Quick setup in the start graphic on the display and adjustment module Carry out the following steps in the below sequence You can find Extend...
Page 12: ...set on the measured value Min adjustment In this menu item you carry out the min adjustment for level Enter the percentage value and the corresponding pressure value for the min level Max adjustment I...
Page 13: ...value and the corresponding density value for the min density Max adjustment In this menu item you carry out the max adjustment for density Enter the percentage value and the corresponding density va...
Page 14: ...variable correctly an allocation of the output signal to 0 and 100 must be carried out adjustment When using the application Level the hydrostatic pressure e g with full and empty vessel is entered as...
Page 15: ...AI FB 1 Channel scaling damping Display Settings e g for language measured value display lighting Diagnosis Information e g on instrument status peak indicator measurement reliability AI FB 1 simulati...
Page 16: ...tment Released Menu item Default value Menu language Order specific Displayed value 1 Signal output in Displayed value 2 Measuring cell temperature in C Backlight Switched on Menu item Parameter Defau...
Page 17: ...t Unit kg s Adjustment 0 corresponds to 0 kg s 100 corresponds to 1 kg s Menu item Parameter Device name Device name Instrument version Hardware and software version Factory calibration date Date Prof...
Page 18: ...luetooth 1 Switch On Bluetooth active Off Bluetooth not active The security concept of Bluetooth operation absolutely requires that the default setting of the sensor PIN be changed This prevents unau...
Page 19: ...art PACTware and the VEGA project assistant Select the device search via Bluetooth and start the search function The device auto matically searches for Bluetooth capable devices in the vicinity The me...
Page 20: ...20 6 Set up with smartphone tablet PC notebook via Bluetooth VEGADIF 85 Profibus PA 53575 EN 230814 Fig 9 Example of an app view Setup sensor adjustment App view...
Page 21: ...d Ex d instruments 12 mA 0 5 mA Electromechanical data version IP66 IP67 and IP66 IP68 0 2 bar 1 Options of the cable entry Cable entry M20 x 1 5 NPT Cable gland M20 x 1 5 NPT cable see below table Bl...
Page 22: ...22 Notes VEGADIF 85 Profibus PA 53575 EN 230814...
Page 23: ...23 Notes VEGADIF 85 Profibus PA 53575 EN 230814...
Page 24: ...ing scope of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change withou...