V
ersion
,
nominal measuring range
D
ead time t
1
T
ime constant t
2
B
asic version
10
bar and
30
bar
100
ms
250
ms
B
asic version
100
mbar
100
ms
180
ms
B
asic version
500
mbar
100
ms
180
ms
B
asic version
,
3
bar
100
ms
180
ms
B
asic version
16
bar and
40
bar
100
ms
180
ms
C
hemical seal version
,
all nominal measuring ranges
D
ependent on the chemi
-
cal seal
D
ependent on the chemi
-
cal seal
R
esponse time with
F
oundation
F
ieldbus
-
cyclically approx
.
10
ms
-
acyclically approx
.
50
ms
D
amping
(
63
%
of the input variable
)
0
…
999
s
,
adjustable
A
dditional output parameter
-
temperature
P
rocessing is made via output signal
HART
multidrop
,
P
ro
fi
bus
PA
and
F
oundation
F
ieldbus
R
ange
-
50
…
+
150
°
C
(-
58
…
+
302
°
F
)
R
esolution
1
°
C
(
1
.
8
°
F
)
A
ccuracy in the range of
0
…
+
100
°
C
(
+
32
…
+
212
°
F
)
±
3
K
A
ccuracy in the range of
-
50
…
0
°
C
(-
58
…
+
32
°
F
)
and
+
100
…
+
150
°
C
(
+
212
…
+
302
°
F
)
typ
.
±
3
K
I
nput variable
M
easured variable
D
i
ff
erential pressure
,
fl
ow and level derived from it
A
djustment di
ff
erential pressure
A
djustment range of the zero
/
span adjustment relating to the nominal measuring range
:
-
P
ressure value zero
-
120
…
+
120
%
-
P
ressure value span
zero
+
(-
220
…
+
220
%
)
9
)
A
djustment level
A
djustment range of the min
./
max
.
adjustment relating to the nominal measuring range
:
-
P
ercentage value
-
10
…
+
110
%
-
P
ressure value
-
120
…
+
120
%
10
)
A
djustment
fl
ow
9
)
V
alues less than
-
1
bar cannot be set
.
10
)
V
alues less than
-
1
bar cannot be set
.
VEGADIF
65
•
F
oundation
F
ieldbus
79
11
S
upplement
36130
-
EN
-
110510