9 Supplement
VEGACAP 35 • Relay (DPDT)
33759-EN-230510
9 Supplement
9.1 Technical data
General data
Material 316L corresponds to 1.4404 or 1.4435
Materials, wetted parts
Ʋ Process fitting - thread
Steel St 37, 316Ti or Aluminium
Ʋ
Process seal
Klingersil C-4400
Ʋ
Insulation (partly insulated)
PE/PA 12
Ʋ
Probe (cable PE/PA 12 partly insu-
lated: ø 6 mm/0.236 in)
316L
Ʋ
Gravity weight
316L
Materials, non-wetted parts
Ʋ
Housing
Plastic PBT (polyester), Alu die-casting powder-coated
Ʋ
Seal between housing and housing lid Silicone
Ʋ
Ground terminal
316L
Ʋ
Cable gland
PA, stainless steel, brass
Ʋ
Sealing, cable gland
NBR
Ʋ
Blind plug, cable gland
PA
Process fittings
Ʋ
Pipe thread, cylindrical (DIN 3852-A) G1½
Ʋ
Pipe thread, conical (ASME B1.20.1) 1½ NPT
Weight
Ʋ
Instrument weight (depending on
process fitting)
0.8 … 4 kg (0.18 … 8.82 lbs)
Ʋ
Gravity weight
approx. 900 g (32 oz)
Ʋ
Cable weight: ø 6 mm (0.236 in)
approx. 180 g/m (1.9 oz/ft)
Sensor length (L)
400 … 20000 mm (15.75 … 787.4 in)
Active tip (gravity weight)
200 mm (7.874 in)
Max. tensile load (cable)
Ʋ
PE/PA 12 partly insulated: ø 6 mm
(0.236 in)
10 KN (2248 lbs)
Max. torque (process fitting - thread)
100 Nm (74 lbf ft)
Torque for NPT cable glands and Conduit tubes
Ʋ
Plastic housing
max. 10 Nm (7.376 lbf ft)
Ʋ
Aluminium housing
max. 50 Nm (36.88 lbf ft)
Measuring frequency
430 kHz
Output variable
Output
Relay output (DPDT), 2 floating change-over contacts
Switching voltage
Ʋ
Min.
10 mV