4 Mounting
VEGABAR 87 • Modbus and Levelmaster protocol
46297-EN-220624
4 Mounting
4.1 General instructions
Note:
For safety reasons, the instrument must only be operated within the
permissible process conditions. You can find detailed information on
the process conditions in chapter "
Technical data
" of the operating
instructions or on the type label.
Hence make sure before mounting that all parts of the instrument ex-
posed to the process are suitable for the existing process conditions.
These are mainly:
•
Active measuring component
•
Process fitting
•
Process seal
Process conditions in particular are:
•
Process pressure
•
Process temperature
•
Chemical properties of the medium
•
Abrasion and mechanical influences
Protect your instrument against moisture ingress through the following
measures:
•
Use a suitable connection cable (see chapter "
Connecting to
power supply
")
•
Tighten the cable gland or plug connector
•
Lead the connection cable downward in front of the cable entry or
plug connector
This applies mainly to outdoor installations, in areas where high
humidity is expected (e.g. through cleaning processes) and on cooled
or heated vessels.
Note:
Make sure that during installation or maintenance no moisture or dirt
can get inside the instrument.
To maintain the housing protection, make sure that the housing lid is
closed during operation and locked, if necessary.
Devices with threaded fitting are screwed into the process fitting with
a suitable wrench via the hexagon.
See chapter "
Dimensions
" for wrench size.
Warning:
The housing or the electrical connection may not be used for screw-
ing in! Depending on the device version, tightening can cause dam-
age, e. g. to the rotation mechanism of the housing.
Avoid damages on the device by lateral forces, for example by vibra-
tions. It is thus recommended to fix the devices with process fitting
Process conditions
Protection against mois-
ture
Screwing in
Vibrations