50
8 Diagnosis, asset management and service
VEGABAR 83 • Modbus and Levelmaster protocol
46295-EN-131107
Code
Text mes-
sage
Cause
Rectification
F265
Measurement
function dis-
turbed
– Sensor no longer carries
out a measurement
– Carry out a reset
– Disconnect operating volt-
age briefly
F266
Impermissi-
ble operating
voltage
– Operating voltage below
specified range
– Check electrical connection
– if necessary, increase
operating voltage
The following table shows the error codes and text messages in the
status message "
Function check
" and provides information on causes
as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
C700
Simulation ac-
tive
– A simulation is active
– Finish simulation
– Wait for the automatic end
after 60 mins.
The following table shows the error codes and text messages in the
status message "
Out of specification
" and provides information on
causes as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
S600
Impermissi-
ble electronics
temperature
– Temperature of the elec-
tronics in the non-specified
section
– Check ambient temperature
– Isolate electronics
– Use instrument with higher
temperature range
S603
Impermissi-
ble operating
voltage
– Operating voltage below
specified range
– Check electrical connection
– if necessary, increase
operating voltage
The following table shows the error codes and text messages in the
status message "
Maintenance
" and provides information on causes
as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
M500
Error in the
delivery sta-
tus
– Stored delivery status is
incorrect
– Send instrument for repair
Function check
Out of specification
Maintenance