4 Mounting

Process module • VEGABAR series 80

1013720-EN-220826

1

Fig. 5: Double chamber housing
1  Position of the screw

4.  Remove the housing

4.3  Mounting steps new process component

1.  Place the housing onto the new process component.
2.  Depending on the housing, tighten the locking screw on the base 

with a screwdriver

3.  Insert the locking ring with the pliers
4.  Tighten the screws of the limit angle and the locking ring with a 

Phillips screwdriver size 1

5.  Insert the electronics module carefully.

Information:

Make sure that the plug is in the correct position. The marking notch 

must be in position "18.00 h".

1

Fig. 6: Plug position
1 Notch

6.  Tighten the two holding screws with a screwdriver (Torx size T 10 

or slot size 4)

7.  Connect the connection cables according to the operating 

instructions manual of the respective sensor

8.  Screw the housing lid back on
The process component is exchanged.
As a rule, the exchange of the process component must be docu-

mented internally when used in Ex applications.

Summary of Contents for VEGABAR 80 Series

Page 1: ...Operating Instructions Process module VEGABAR series 80 Document ID 1013720...

Page 2: ...ng transport and storage 5 4 Mounting 6 4 1 Mounting preparations 6 4 2 Dismounting steps previous process component 6 4 3 Mounting steps new process component 8 5 Setup 9 5 1 Setup 9 6 Dismount 10 6...

Page 3: ...n refers to the Docu ment ID By entering the Document ID on www vega com you will reach the document download Information note tip This symbol indicates helpful additional infor mation and tips for su...

Page 4: ...ics module emitting electronics housing or process compo nents are replacement components for existing sensors 2 3 Environmental instructions Protection of the environment is one of our most important...

Page 5: ...transport packaging Nonobservance of these instructions can cause damage to the device The delivery must be checked for completeness and possible transit damage immediately at receipt Ascertained tran...

Page 6: ...electronics compartment The below illustrations show the respective position of the electronics compartment in a single or double chamber housing 1 Fig 1 Single chamber housing 1 Position of the elect...

Page 7: ...opening levers Proceed as follows 1 Loosen the screws of the limit bracket and the locking ring with a Phillips screwdriver size 1 2 1 3 Fig 4 Position of the screws and locking ring in the example o...

Page 8: ...and the locking ring with a Phillips screwdriver size 1 5 Insert the electronics module carefully Information Make sure that the plug is in the correct position The marking notch must be in position 1...

Page 9: ...9 5 Setup Process module VEGABAR series 80 1013720 EN 220826 5 Setup 5 1 Setup Setup is carried out according to the operating instructions manual of the respective sensor...

Page 10: ...Disposal Pass the instrument on to a specialised recycling company and do not use the municipal collecting points Remove any batteries in advance if they can be removed from the device and dispose of...

Page 11: ...11 7 Supplement Process module VEGABAR series 80 1013720 EN 220826 7 Supplement 7 1 Technical data Technical data are stated in the operating instructions manual of the respective sensor...

Page 12: ...12 Notes Process module VEGABAR series 80 1013720 EN 220826...

Page 13: ...13 Notes Process module VEGABAR series 80 1013720 EN 220826...

Page 14: ...14 Notes Process module VEGABAR series 80 1013720 EN 220826...

Page 15: ...15 Notes Process module VEGABAR series 80 1013720 EN 220826...

Page 16: ...ning scope of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change witho...

Reviews: