l
sensor
_
range
-
"
S
ensor
_
range
.
unit
'
refers to
'
S
ensor
_
value
'
,
'
M
ax
/
M
in
_
peak
_
sensor
_
value
'
,
'
C
al
_
point
_
hi
/
lo
'
-
includes sensor unit
:
bar
,
PSI
…;
only unit part of
DS
-
68
is writable
l
simulate
_
primary
_
value
l
simulate
_
secondary
_
value
_
1
l
simulate
_
secondary
_
value
_
2
l
device status
-
"
0
:
""
OK
""
13
:
""
non
-
speci
fi
c error
""
17
:
""
C
al span too small
""
34
:
""
EEPROM
memory fault
""
36
:
""
ROM
memory fault
""
37
:
""
RAM
memory fault
""
40
:
""
non
-
speci
fi
c hardware fault
""
41
:
""
S
ensor
element not found
""
42
:
""
N
o leaking pulse
""
43
:
""
N
o trigger signal
""
44
:
""
EMI
error
""
113
:
""
C
ommunication hardware fault
"""
l
linearization type
-
P
ossible types of linearization are
:
linear
,
user de
fi
ned
,
cylindrical lying container
,
spherical
container
-
"
0
:
""
L
inear
""
1
:
""
U
ser def
""
20
:
""
C
ylindrical lying container
""
21
:
""
S
pherical container
"""
l
curve
_
points
_
1
_
10
-
X
and
Y
values for the user de
fi
ned linearization curve
l
curve
_
points
_
11
_
20
-
X
and
Y
values for the user de
fi
ned linearization curve
l
curve
_
points
_
21
_
30
-
X
and
Y
values for the user de
fi
ned linearization curve
l
curve
_
points
_
31
_
33
-
X
and
Y
values for the user de
fi
ned linearization curve
l
curve status
-
R
esult of table plausibility check
-
"
0
:
""
U
ninitialized
""
1
:
""
G
ood
""
2
:
""
N
ot monotonous increasing
""
3
:
""
N
ot monotonous
decreasing
""
4
:
""
N
ot enough values transmitted
""
5
:
""
T
oo many values transmitted
""
6
:
""
G
radient of edge too high
""
7
:
""
V
alues not excepted
""
8
:
""
T
able currently loaded
""
9
:
""
S
orting
and checking table
"""
l
SUB
_
DEVICE
_
NUMBER
l
SENSOR
_
ELEMENT
_
TYPE
-
0
:
"
non
-
speci
fi
c
"
l
display
_
source
_
selector
-
S
elects the type of value that is displayed on the indication
-/
adjustement
-
module
-
"
0
:
""
P
hysical value
""
1
:
""
P
ercent value
""
2
:
""
L
in percent value
""
6
:
""
O
ut
(
AI
1
)
""
7
:
""
L
evel
""
8
:
""
O
ut
(
AI
2
)
""
9
:
""
O
ut
(
AI
3
)
"""
l
max
_
peak
_
sensor
_
value
-
H
olds the maximum sensor value
.
W
rite access resets to current value
.
U
nit derives from
'
S
ensor
_
range
.
unit
'
-
W
rite access resets to current value
l
min
_
peak
_
sensor
_
value
-
H
olds the minimum sensor value
.
W
rite access resets to current value
.
U
nit derives from
'
S
ensor
_
range
.
unit
'
-
W
rite access resets to current value
l
CAL
_
POINT
_
HI
VEGABAR
64
•
F
oundation
F
ieldbus
65
10
S
upplement
28259
-
EN
-
081209