M
easured value on the indicating and adjustment module does not
correspond to the value in the
PLC
l
T
he menu item
"
D
isplay
-
D
isplay value
"
is not set to
"
AI
-
O
ut
"
à
C
heck values and correct
,
if necessary
?
I
nstrument does not appear during connection setup
l
I
ncorrect termination
à
C
heck termination at the beginning and end points of the bus
and terminate
,
if necessary
,
according to the speci
fi
cation
l
I
nstrument not connected to the segment
à
C
heck and correct
I
n
E
x applications
,
the regulations for the wiring of intrinsically safe
circuits must be observed
.
?
E
013
l
no measured value available
9
)
à
E
xchange instrument or return instrument for repair
?
E
017
l
A
djustment span too small
à
repeat with modi
fi
ed values
?
E
036
l
no operable sensor software
à
C
arry out a software update or send the instrument for repair
?
E
041
l
H
ardware error
,
electronics defective
à
E
xchange instrument or return instrument for repair
?
E
113
l
C
ommunication con
fl
ict
à
E
xchange instrument or return instrument for repair
D
epending on the failure reason and measures taken
,
the steps
described in chapter
"
S
et up
"
must be carried out again
,
if necessary
.
9
)
F
ault message can also appear if the pressure is higher than the nominal
range
.
F
ault messages via the
indicating
/
adjustment
module
R
eaction after fault rec
-
ti
fi
cation
48
VEGABAR
64
•
F
oundation
F
ieldbus
8
M
aintenance and fault recti
fi
cation
28259
-
EN
-