5 Setup
Electronics module • SOLITRAC, MINITRAC, POINTRAC, WEIGHTRAC
40104-EN-210107
5 Setup
5.1 Setup preparations
If you ordered the electronics module
by stating the sensor serial
number
, it is ready for the setup procedure immediately after installa-
tion and connection to power supply.
Electronics modules for SIL qualified instruments can only be ordered
by stating the sensor serial number.
If you ordered the electronics module
without programming
or you
are using a suitable electronics module from stock, you first have to
load the instrument data after the installation.
The instrument data also include the TAG no., information on the
process fitting and seal as well as activation data for a supplementary
electronics.
Enter the serial number of your device into the search field on our
homepage " www.vega.com".
After entering the serial number, the order data of the device are
displayed.
Under "
Related documentation
" you will find "
Sensor for electronics
exchange
" as an XML file. Save this DTM configuration file with "
Save
as
" on your PC and transfer it via PACTware and the Service DTM to
the instrument.
5.2 Setup steps
If the instrument is used in the same application after the electronics
exchange, the previous parameter settings of the instrument must be
restored. To do this, you can use the import function of the adjustment
software PACTware with the device DTMs or the copy function of the
display and adjustment module.
If no copy of the parameter settings is available, you have to carry out
a fresh setup. See the operating instructions of the sensor.
On SIL qualified instruments, the settings of the electronics must be
checked and verified after the electronics exchange. Only then is the
instrument again ready for operation.
With sensor serial num-
ber
Electronics module with-
out programming
Parameter adjustment