H
ow to interrupt the simulation
:
à
P
ush
[
ESC
]
I
nformation
:
T
he simulation is terminated automatically
10
minutes after the last key
has been pushed
.
I
n this menu item
,
you select the measured variable of the system
.
A
linearization is necessary for all vessels in which the vessel volume
does not increase linearly with the level
-
e
.
g
.
in a horizontal cylindrical
or spherical tank
-
and the indication or output of the volume is
required
.
C
orresponding linearization curves are preprogrammed for
these vessels
.
T
hey represent the correlation between the level
percentage and vessel volume
.
T
he linearisation applies to the
measured value indication and the current output
.
B
y activating the
appropriate curve
,
the volume percentage of the vessel is displayed
correctly
.
I
f the volume should not be displayed in percent but e
.
g
.
in l
or kg
,
a scaling can be also set in the menu item
"
D
isplay
"
.
C
aution
:
N
ote the following
,
if the respective sensor is used as part of an over
fi
ll
protection system according to
WHG
:
I
f a linearisation curve is selected
,
the measuring signal is no longer
compulsorily linear proportional to the level
.
T
his must be taken into
consideration by the user
,
particularly when adjusting the switching
point on the level switch
.
A
dditional settings
/
D
e
-
vice settings
F
urther settings
/
L
inear
-
ization
I
ndicating and adjustment module
PLICSCOM
27
6
S
et up
-
S
ensors from
HW
2
.
0
.
0
and
SW
4
.
0
.
0
36433
-
EN
-
091104