4
C
onnecting to power supply
4
.
1
P
reparing the connection
N
ote safety instructions
A
lways keep in mind the following safety instructions
:
l
C
onnect only in the complete absence of line voltage
l
I
f overvoltage surges are expected
,
overvoltage arresters
should be installed
T
ip
:
W
e recommend
VEGA
overvoltage arresters
B
61
-
300
(
external energy
)
and
B
62
-
36
G
(
sensor supply
).
T
ake note of safety instructions for
E
x applications
I
n hazardous areas you should take note of the appro
-
priate regulations
,
conformity and type approval certi
fi
-
cates of the sensors and power supply units
.
S
elect power supply
T
he voltage supply for the
E
x separator
VEGATRENN
149
AE
x
must be in the rangeof
20
…
250
V AC
,
50
/
60
H
z or
20
…
250
V DC
.
S
electing connection cable
F
or power supply of
VEGATRENN
149
AE
x
,
an approved instal
-
lation cable with
PE
conductor is necessary
.
T
he sensor or the signal conditioning instrument are connected
with standard two
-
wire cable to the separator
.
I
f strong electro
-
magnetic interference is expected
,
screened cable should be
used
.
C
able screening and grounding
I
f screened cable is used
,
connect the cable screen on both ends
to ground potential
.
I
n the sensor
,
the screen must be connected
directly to the internal ground terminal
.
T
he ground terminal on the
outside of the housing must be connected to the potential equal
-
isation
.
I
f potential equalisation currents are expected
,
the screen con
-
nection on the separator or signal processing instrument must be
made via a ceramic capacitor
(
e
.
g
.
1
n
F
,
1500
V
).
T
he low fre
-
quency potential equalisation currents are thus suppressed
,
but
the protective e
ff
ect against high frequency interference signals
remains
.
S
elect connection cable for
E
x applications
T
ake note of the corresponding installation regulations
for
E
x applications
.
I
n particular
,
make sure that no po
-
tential equalisation currents
fl
ow over the cable screen
.
I
n case of grounding on both sides this can be achieved
by the use of a capacitor or a separate potential equal
-
isation
.
4
.
2
W
iring plan
E
x separator
VEGATRENN
149
AE
x
0+H
0+
0- L/+
N/-
0+H
0+
0-
L/+
N/-
I+
I-
1
2
3
4
F
ig
.
7
:
T
erminal assignment
VEGATRENN
149
AE
x
1
S
ensor circuit
2
P
rocessing circuit
3
P
ower supply
4
HART
communication sockets
C
onnecting to power supply
S
eparating and protective instruments
–
S
eparating and protective instruments
7
31996
-
EN
-
071204