11
3 Mounting
FIBERTRAC 32 • Four-wire 4 … 20 mA/HART
62071-EN-211203
L1
L2
h
1
Fig. 5: Installation position - cascading arrangement
h Summed measuring range
L Measurement length (L1, L2)
1 Red marking line for designating the measuring range
Here, one instrument acts as a Primary and all other instruments
operate as Summation Secondary. The pulse rates of all instruments
are summed in the Primary instrument and converted into a common
signal.
If several sensors are cascaded, the measuring ranges of the indi
-
vidual detectors must directly join each other. The detectors must also
slightly overlap.
Make sure that the red marking lines directly join the measuring range
of the next FIBERTRAC 32.
Mount the FIBERTRAC 32 in such a way that the detector hose
is directly in the radiated area of the source container. Mount the
FIBERTRAC 32 preferably side by side and make sure that no detec-
tor hose is hidden by another sensor.
On vessels with temperature insulation, the sensor and the source
container should be preferably mounted outside of the tank insulation.
Vessel with heat insula-
tion