Vega SH-2 / User Manual
29
Revision 06 – 06 July 2020
"temp":28,
"onewire":[28.2, 27.9, 28.3, 0, 0, 0, 0, 0, 0, 0],
}
}
Transcription of the message fields:
Message – part with information about current message.
firmware – name and version of the device firmware
num – number of the message sent by the SH-02 device
date – date of the message sending
time – time of the message sending
LBS – part with information about the gateway parameters which resend that packet
TAC, CID, MCC, MNC – gateway identifications
ACT– technology (9 – LTE Cat.NB1)
SQ – gateway signal quality
CellStatus – part with information about the cellular state
EARFCN – the number of radio frequency channel (absolute)
PCID – physical network address
RSRP – input signal power
RSRQ – input signal quality
RSSI – indicator of the input signal power
SNR – signal to noise ratio
Telemetry – part with collected data (one packet)
reason – transmitting reason
date – date of the data collection
time – time of the data collection
bat – battery charge
pulse1 – pulse number on the input 1
pulse2 – pulse number on the input 2
ADC1 – voltage value on the analog input 1
ADC2 – voltage value on the analog input 2
temp – temperature of the processor
onewire – external temperature sensors’ readings
modbus
– data from the RS-485 interface from an external MODBUS device (10
values of 16-bit register)
2
If the MODBUS mode on, then that data will transmit instead of onewire data and vice versa