Manually Starting/Stopping Tank Leak Tests
Use this screen to manually start or stop a Tank Leak Test.
[112, 114, 129-130] Manual Test Start/Stop Screen
Legend for numbered boxes
1
2
3
4
5
6
1
01-01-2000
12:00 AM
ALL FUNCTIONS NORMAL
2
3
4
5
MANUAL TANK TEST
[129]
TANK 1
[130]
[112]
[114]
6
0.76 LPH
1
Test Method [129] - Select Single Tank or All Tanks.
Touch the Down Arrow button to the right of the window
and enter the desired choice.
2
Test Control [130] - Select Timed Duration or Manual
Stop (test runs until you stop it, or for 24 hours,
whichever comes first). Touch the Down Arrow button to
the right of the window and enter the desired choice.
3
Test Rate [112] - Select a leak test rate of 0.2 gph (0.76
lph) (default) or 0.1 gph (0.38 lph). The 0.1 gph (0.38
lph) rate requires a Mag 1 Probe. Touch the Down Arrow
button to the right of the window and enter the desired
choice.
4
Test Duration [114] - Select a test duration of from 0 to
24 hours. There is a minimum duration of two hours for
0.2 gph (0.76 lph) tests and three hours for 0.1 gph
(0.38 lph) tests. Default is 2 hours.
Note: this window only appears if you selected Timed
Duration in the Test Control window. Touch the Down
Arrow button to the right of the window and enter the
desired choice.
5
Test Start button - Touch this button to begin
the test.
6
Test Stop button - Touch this button to stop a
tank leak test.