background image

Setup

Output Relay Setup - VST ECS Membrane Processor & VST Green Machine

8

Output Relay Setup - VST ECS Membrane Processor & VST Green Machine

The Output Relay setup programs an output relay so that the TLS console can switch a controlled vapor processor 
on and off as shown in Figure 4

Figure 4.

Output Relay Setup for VST ECS Membrane Processor

Figure 5 shows example setup printouts of the Output Relays setup.

Figure 5.

Output Relay Setup Printout Examples for TLS Console Controlled Processor

SETUP MODE

PRESS <FUNCTION> TO CONT

OUTPUT RELAY SETUP
PRESS <STEP> TO CONTINUE

Prints out a copy of the Output Relay Setup entries. See examples in figure below. 
In our example R1 is the relay used by PMC to control the processor, R2 is the relay 
used to shutoff the processor when the High Product Alarm is active.

M

P

S

S

S

F

ENTER RELAY DESIGNATION
R1 :  

R1 : SELECT RELAY TYPE
STANDARD

R2 : SELECT RELAY TYPE
STANDARD

R2 : SELECT TANK
NONE

R1 : SELECT ORIENTATION
NORMALLY OPEN

R2 : SELECT ORIENTATION
NORMALLY OPEN

R2 : VP SHUTOFF
IN-TANK ALARMS: NO

Press Change 
and enter
VAPOR PROCESSOR
for the relay

Note: If using an I/O 
Combo Module
there are just 2 slots.

801-6.eps

C

Press Change 
and enter
VP SHUTOFF
for the relay

C

C

E

S

E

S

E

S

RELAY CONFIG - MODULE X
SLOT # — X, X, X, X

T

ENTER RELAY DESIGNATION
R2 :  

S

S

C

E

S

Vapor Processor
Standard

C

E

S

Standard
Vapor Processor

C

E

S

E

S

Normally Open
Normally Closed

Normally Closed
Normally Open

C

E

S

YES
NO

R2 : IN-TANK ALARMS
HI PRODUCT: NO TANKS

C

E

S

ALL TANKS
NO TANKS

C

Change

B

Backup

M

Mode

E

Enter

S

Step

F

Function

Print

T

P

1

2

Key press
sequence

Repress until
desired message
appears in display

Key Legend

Tank

Sensor

Press once and
the 2nd X changes
 to a 2. 

C

C

Press once and the first 
position blinks, press 
again and the X changes 
to a 1.

Press once and 
the second 
position blinks

OUTPUT RELAY SETUP

----------------------

  

R 1: VAPOR PROCESSOR

TYPE:

 VAPOR PROCESSOR

NORMALLY OPEN

- NO ALARM ASSIGNMENTS -

OUTPUT RELAY SETUP

----------------------

  

R 2: VP SHUTOFF

TYPE:

 STANDARD

NORMALLY CLOSED

IN-TANK ALARMS

ALL HIGH PRODUCT ALARMS

i

s

d-evr\ortl

s

cntrlvp

s

etprt.ep

s

Summary of Contents for TLS

Page 1: ...Manual No 577013 801 Revision E Install Setup Operation Manual Pressure Management Control For VST Processors...

Page 2: ...the claim with the carrier and replace the damaged missing product at no charge to the customer Customer Service will work with production facility to have the replacement product shipped as soon as...

Page 3: ...t Card for Vapor Processor Communication 5 TLS Console with VST ECS Membrane Processor 5 Setup Introduction 7 Smart Sensor Setup 7 Output Relay Setup VST ECS Membrane Processor VST Green Machine 8 PMC...

Page 4: ...to TLS console for serial communication 14 Figure 12 Connection Description window 15 Figure 13 Connect To window 15 Figure 14 Console comm port settings printout example 16 Figure 15 HyperTerminal ma...

Page 5: ...n Requirements Veeder Root requires the following minimum training certifications for contractors who will install and setup the equipment discussed in this manual Installer Level 1 Certification Cont...

Page 6: ...al 576013 637 ELECTRICITY High voltage exists in and is sup plied to the device A potential shock hazard exists TURN POWER OFF Live power to a device creates a potential shock hazard Turn Off power to...

Page 7: ...ace modules can be installed Comm bay Power bay and Intrinsically Safe bay ref Figure 1 Probe Interface modules and Smart Sensor modules are installed in the Intrinsically Safe bay and the Mod Bus mod...

Page 8: ...y not be relocated to other terminals without reprogramming the system Grounding Probe and Sensor Shields Connect probe and sensor cable shields to ground at the console only Do not ground both ends o...

Page 9: ...ct the vapor processor motor control relay to two relays on either the 4 Relay or I O Combination module as shown in Figure 2 Multiport Card for Vapor Processor Communication A Multiport card is neede...

Page 10: ...onnector COMMUNICATION BAY POWER BAY I S BAY RELAY RELAY RATINGS Form C Contacts 120 VAC 2A Max or 24 VDC 2A Max 1 2 4 RELAY OUTPUT MODULE NC NO C 1 NC NO C 2 3 NC NO C 3 NC NO C 4 4 Rigid Conduit ent...

Page 11: ...vance Cursor Print T P 1 2 Key press sequence Repress until desired message appears in display Key Legend Tank Sensor S 801 7 eps C C E S E S E S P F SMARTSENSOR SETUP PRESS STEP TO CONTINUE SETUP MOD...

Page 12: ...E R1 SELECT ORIENTATION NORMALLY OPEN R2 SELECT ORIENTATION NORMALLY OPEN R2 VP SHUTOFF IN TANK ALARMS NO Press Change and enter VAPOR PROCESSOR for the relay Note If using an I O Combo Module there a...

Page 13: ...PROCESSOR VST GREEN MACHINE Sets vapor processor On point Range Off setting On setting 3 For more info see example at right Vapor Processor On Off example P V valve opens Absolute Range IWC Ullage vap...

Page 14: ...exists the display will continuously cycle through the appropriate alarm messages The system automatically prints an alarm report showing the alarm type its location and the date and time the alarm co...

Page 15: ...type of alarm and the time the alarm was posted Alarm example in Figure 9 PMC Alarms are logged into the Priority Alarm History in the TLS Figure 9 TLS console alarm example MMM DD YYYY HH MM XM VP E...

Page 16: ...ON FAIL 2nd Consecutive mass emission failure Red PMC SETUP FAIL PMC is not configured or missing components Red Troubleshooting Guide www vsthose com See ISD Troubleshooting Guide P N 577013 819 Exhi...

Page 17: ...MM SS XM ALL FUNCTIONS NORMAL EFFLUENT EMISSIONS TEST STATUS PASS VP DUTY CYCLE TEST STATUS PASS 801 8 eps Prints out a copy of the PMC Status report See example at right ECS Membrane Processor Only...

Page 18: ...le DB9 DB25 DB9 female DB9 male DB9 male RS 232 card DB25 female Slots 1 2 or 3 ATEN USB to DB9 serial adapter Serial I O PC Card Plugs into PCMCIA port Multiport card DB9 female Slot 4 Laptop USB mal...

Page 19: ...After clicking the OK button you may see a repeat of the modem dialing windows in which case ignore cancel them all 4 When the Connect To window appears Figure 13 depending on your connection method...

Page 20: ...rity Code is disabled If the code was enabled you would see a 6 digit number which you will need to enter to access the console refer to the Sending Console Commands paragraph below for more informati...

Page 21: ...e the window s and return to the main screen If the RS 232 Security Code is disabled press and hold the Ctrl key while you press the A key then type in IV8200 If the RS 232 Security Code is enabled e...

Page 22: ...History Report See example Figure 20 SOH I11200 SOH Control A For more information on TLS console serial commands refer to the V R Serial Interface Manual SOH IV8200 JUN 1 2002 8 07 AM SITE NAME SITE...

Page 23: ...5 03AM 26 60 0 221 0 205 NO 3 09 07 1 15PM 17 92 0 278 0 268 NO 3 10 07 3 01AM 7 70 0 200 0 223 NO 3 10 07 4 30AM 4 02 0 202 0 224 NO 3 10 07 7 54PM 23 62 0 306 0 245 NO 3 11 07 11 24PM 6 55 0 256 0...

Page 24: ...Name Site Address Site Address Site Address PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 2 TANK Premium 91 PROBE OUT CLEAR 4 04 08 12 14PM T 2 TANK Premium 91 PROBE OUT...

Page 25: ...DESCRIPTION ALARM TYPE STATE DATE TIME T 3 TANK DIESEL LOW TEMP WARNING CLEAR 12 08 10 3 00PM T 3 TANK DIESEL LOW TEMP WARNING ALARM 12 08 10 3 00PM T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 12 08 10...

Page 26: ...utomatic changing the control mode to Manual mode will turn the PMD off When set to Manual mode the system will revert to Automatic mode after 4 hours PMC Diagnostic Menu Figure 21 PMC Diagnostic Menu...

Page 27: ...For technical support sales or other assistance please visit www veeder com...

Reviews: