POS App Guide

DIM Installation Examples

40

GasBoy CFN Systems

TLS CONSOLE SOFTWARE REQUIREMENTS

TLS-350R with BIR Software Requirements
• System software Version 17 (or higher)

VEEDER-ROOT HARDWARE REQUIREMENTS (REF. TABLE 2)

The following equipment is required to interface the TLS to the Gasboy CFN system:
• One Gasboy Dispenser Interface Module 

• One installation kit 

 GASBOY SYSTEM REQUIREMENTS FOR BIR INTERFACE

• Console must be Site Controller II, version 2.0 or later and have “Send All Messages” feature.

• GasBoy junction box (P/N C05020).

• All Profit Point Broadcast messaging enabled.

• Non-blended dispensers (not a restriction for ISD only applications).

CONNECTING TO THE SITE CONTROLLER II

The TLS-350R must be connected to the Console Loop of the Site Controller II to receive BIR data from the CFN 
(see Figure 23).

Summary of Contents for TLS Series

Page 1: ...Manual No 577013 401 Revision K Application Guide TLS Consoles Point of Sale POS...

Page 2: ...al or consequential damages in connection with the furnishing performance or use of this publication The information contained in this publication may be subject to change without notice This publicat...

Page 3: ...Module TDIM TLS 350R 6 TCP IP DIM TDIM TLS 450 TLS 450PLUS 6 DIM And Installation Kit Ordering Guide 7 DIM Installation Examples Bennett POS System 16 Veeder Root Software Requirements 16 Veeder Root...

Page 4: ...are Requirements 37 Installation Notes 37 GasBoy CFN Systems 40 TLS Console Software Requirements 40 Veeder Root Hardware Requirements Ref Table 2 40 GasBoy System Requirements for BIR Interface 40 Co...

Page 5: ...7 Series Pulse Transmitters And Required Barriers 43 Figure 25 Wiring Diagram Of TLS 450 TLS 450PLUS MDIM Using Two 1871 7697 Series Pulse Transmitters Required Barriers 44 Figure 26 Mechanical Dispen...

Page 6: ...apabilities TLS 350R WITH BIR ONLY AND TLS 350R WITH BIR AND ISD Support up to 36 fueling positions Support up to 6 meters hoses per fueling position Support manifolded tanks Support blending dispense...

Page 7: ...stallation kits vary for each DIM and include all required adapter boxes and cables IN STATION DIAGNOSTICS TLS 350R with ISD option ECPU2 board with 325 or later software and a NVMEM203 board A Mag 1...

Page 8: ...interface to most Gilbarco Wayne and 3rd Party POS systems that implement the VR BIR Protocol ALLIED ANDI EXCENTUS BENNETT For electronic dispensers one DIM is required for each TLS 450 Up to 3 DIMs c...

Page 9: ...antly evaluating and supporting new applications If your application is not listed in this guide contact your Veeder Root Sales Representative Bennett 92D X Mechanical Mechanical noncomp or Mechanical...

Page 10: ...0PLUS console installs in comm slots 1 or 2 Factory installed in TLS4 console TLS 450 and TLS 450PLUS require module kit P N 330020 665 Various CDIM monitoring applications include current loop RS 232...

Page 11: ...ole system software Version 15 or higher Version 21 or higher is recommended Network connection to a PC requires a hub Connecting to a hub requires a straight CAT 5 cable Direct connection to a PC req...

Page 12: ...r version 2 0 or later is required A Gasboy junction box Gasboy part C05020 should be ordered for installa tion No Blending Net work POS Required ANDI ALLIED ANDI ALLIED NEXTGEN 330280 001 Standard In...

Page 13: ...To support this DIM and the TLS 350R the G site must be upgraded to include the EMC interface Uses Controller types C2 C15 486 and Pen tium Site controllers Passport Passport EDH Y Y Y Verify BIR pro...

Page 14: ...o Blending Wayne Nucleus 330404 200 330020 665 848722 XXX Y Y Y Wayne Nucleus POS with Gilbarco Dispens ers Radiant 330280 001 Standard In Gauge None Y Y Y Radiant Systems Series P1550 set up on the T...

Page 15: ...er Petrovend 331214 001 330020 800 None Y Y Y One or more pulser totalizer kits are needed PN 787491 003 Each mech DIM supports up to 4 mech dispensers Up to 8 may be installed in the high power compa...

Page 16: ...tralia PEC with 8850 POSTEC with RCC Wayne with Mar keter 2000 Sweden Radiant 330280 001 Standard In Gauge None Y Y Y Radiant Systems Series P1550 set up on the TLS must have a DIM string pro grammed...

Page 17: ...s Series P1550 set up on the TLS must have a DIM string pro grammed in The DIM string is B9DNHG and needs to be pro grammed in DIM Diag nostics You will need to use a twisted pair RJ 11 cable to the p...

Page 18: ...POSTEC with RCC Wayne with Mar keter 2000 Sweden 67 A 98 331354 001 None 331391 XXX Y N N Tokheim controller only 67 B 848744 XXX Columbus 330280 001 Standard in Gauge None Y Y Y For Rockport cable k...

Page 19: ...in Gauge None Y Y Y TCPIP interface for Wayne IDPOS dis pensers only Radiant 330280 001 Standard in Gauge None Y Y Y Radiant Systems Series P1550 set up on the TLS must have a DIM string pro grammed...

Page 20: ...llation manual Figure 1 Simplified DIM Connections To Various Dispensing Systems Mechanical Dispenser Dispenser Controller Network Junction Box Distribution Box Cable Adaptor Box CDIM LVDIM MDIM EDIM...

Page 21: ...IR and TLS 350R with BIR and ISD Only non blending type 92D dispensers with Orpak controllers are supported TLS 350R with ISD All type 92D dispensers with Orpak controllers are supported INSTALLATION...

Page 22: ...URRENT LOOPS BENNETT PUMP INTERFACE BOX 17 1 2 3 4 5 6 7 8 9 11 12 13 14 15 18 19 20 21 Dispenser Terminal Block 22 16 GRN GROUND YEL DATA ORG DATA YEL DATA ORG DATA GRN CONDUIT shield shield White Bl...

Page 23: ...per current loop The following POS consoles are supported Transac 1e1 PA0132 PA0141 Transac 12 PA0134 PA0142 Transac 12A PA0151 PA0152 Transac 12B PA0173 Transac 12C PA0188 Transac 12G PA0203 TCRG PA...

Page 24: ...RAM FOR A TRANSAC CURRENT LOOP INTERFACE A PA0133 distribution box is shown in Figure 3 below Other box models are slightly different Figure 3 Transac Series Current Loop Interface Shielded 2 Wire Fly...

Page 25: ...ntus Interface Box POS Controller VR CAB P N 330591 00X Gilbarco Distribution Box TLS Console Connects to CDIM Set sw to RUN CONSOLE COMM PUMP COMM RUN BYPASS P N S N Environmental Products VEEDER ROO...

Page 26: ...distribution box PA02420000000 Gilbarco dispenser distribution box PA02610000010 Gilbarco dispenser distribution box PA02610000020 Gilbarco pump controller model PA02410000000 Gilbarco Transac System...

Page 27: ...POS App Guide DIM Installation Examples 22 Figure 5 Universal Distribution Box Interface PAM or Transac 1000 Site Controller cab dim vrgbts eps CDIM connection TLS Console 401 10 eps...

Page 28: ...sitions are supported by the TLS 350R and up to 72 fueling positions are supported by the TLS 450 TLS 450PLUS In dispenser credit card readers CRINDS are supported To support a DIM and the TLS 350R th...

Page 29: ...Adapter Q13180 03 331138 001 G Site C 2 G SITE Tank Gauge Connect RJ 45 plug into 25 pin D RJ 45 Adapter 331138 002 Connect RJ 45 plug into 25 pin D RJ 45 Adapter 331138 001 Connect RJ 45 plug into 2...

Page 30: ...lbarco Dispenser Distribution Box PA0281XXXXXX0 An AutoGas 507 controller is required with the AutoGas Storemaster POS SYSTEM LIMITATIONS Up to 36 Gilbarco single product or blending fueling positions...

Page 31: ...rrent Loop Interface Communications Cable Y cable 2 9 pin D Style connectors POS 401 12 eps Universal Distribution Box AutoGas 510 CRIND Controller with Current Loop Dispenser Interface Module CRIND L...

Page 32: ...With Serial Interface Communications Cable Y cable 2 9 pin D Style connectors 401 13 eps Universal Distribution Box AutoGas 510 CRIND Controller with Serial Interface CRIND Loop Current Loop Cable Ada...

Page 33: ...Controller Communications Cable Y cable 2 9 pin D Style connectors Generic POS 401 14 eps Universal Distribution Box AutoGas 510 CRIND Controller CRIND Loop Current Loop Current Loop Cable Adapter Bo...

Page 34: ...tions Cable 401 15 eps Universal Distribution Box AutoGas 507 CRIND Controller CRIND Loop Current Loop Cable Adapter Box To Cable Adapter Box To Controller UDB Storemaster POS CRIND Loop Computer Conn...

Page 35: ...VEEDER ROOT HARDWARE REQUIREMENTS REF TABLE 2 The following equipment is required to interface the TLS to the SmartCrind network One TCP IP TDIM Interface Module Ethernet cable SYSTEM LIMITATIONS Up t...

Page 36: ...default setting for serial port J4 Version 5 rev 6 dated 11 1989 or later The Tokheim DHC itself can be Standalone and used with a third party POS or An internal component of a Tokheim Vision 100 Vis...

Page 37: ...F 9038 GALS 962 GALS 0 GALS 8950 GALS 81 37 INCHES 28 GALS 1 37 INCHES 74 9 DEG F To Dispensers To Third Party POS Connects to EDIM TLS 350R Console 25 Pin D P N 330408 XXX ALARM WARNING POWER T1 PRE...

Page 38: ...8 GALS 5792 GALS 4792 GALS 4194 GALS 41 02 INCHES 0 GALS 0 00 INCHES 65 0 DEG F 9038 GALS 962 GALS 0 GALS 8950 GALS 81 37 INCHES 28 GALS 1 37 INCHES 74 9 DEG F Cable connects to J7 or J8 on rear panel...

Page 39: ...o the Wayne site controller The dispensers may feature electronic card readers TDIM Installations Wayne IDPOS dispenser software 2 29 TLS 350R and TLS 450 SUPPORTED WAYNE SYSTEMS Wayne 186 System with...

Page 40: ...yne Nucleus Data Box Figure 15 Wayne Dispenser Data Box Current Loop TLS 350R and TLS 450 Figure 16 Wayne IDPOS Dispensers TLS 350R and TLS 450 POS 401 20 eps Cable P N 330592 XXX Cable P N 330592 XXX...

Page 41: ...TB6 1 2 3 4 5 6 Data In Data Out To CAB marked Left To CAB marked Right Left Current Loop Right Current Loop Set adjacent toggle switch to right Auto position Set adjacent toggle switch to right Auto...

Page 42: ...pported by this DIM In dispenser credit readers are supported by the Schlumberger DIM Blending of any type is not supported by the Schlumberger DIM not a restriction for ISD only applications MICROMAX...

Page 43: ...uired 1 2 3 4 To Cable Adaptor Box To MicroMax POS Schlumberger MicroMax 3000 or Equivalent TB1 Note These two 25 pin D connectors are only to be used with Allied Station Site Controller Box Two Condu...

Page 44: ...umberger MicroMax Cable Adapter Box RJ 45 RJ 45 POS CONTROLLER 25 Pin D Tokheim DHC Port 2 Port 5 POS Connects to CDIM TLS 350R Console ALARM WARNING POWER 401 26 eps Cable Adapter Box POS POS CONTROL...

Page 45: ...One Gasboy Dispenser Interface Module One installation kit GASBOY SYSTEM REQUIREMENTS FOR BIR INTERFACE Console must be Site Controller II version 2 0 or later and have Send All Messages feature GasB...

Page 46: ...le Supplied by Gasboy SITE CONTROLLER II To Console or other Junction Boxes ALARM WARNING POWER GND BLUE WHITE STRIPE WHITE BLUE STRIPE ORANGE WHITE STRIPE WHITE ORANGE STRIPE 401 27 eps To Plug In Co...

Page 47: ...nventory protocol commonly used by POS and other systems to collect inventory data from Veeder Root TLS Consoles Table 3 lists POS systems known to have implemented the Veeder Root protocol and thus s...

Page 48: ...er system are supported Requires a pulser totalizer or pulse transmitter and a safe barrier device for each fueling position Only Veeder Root mechanical dispensers are supported Typical Wiring to Mech...

Page 49: ...eps Barrier P N 7859 Barrier P N 7859 769780 012 Pulse Transmitter 769780 012 Pulse Transmitter Blue Black Orange Orange Blue Black Orange Blue Orange Blue Orange White 120 Vdc 120 Vdc White Orange N...

Page 50: ...POS App Guide DIM Installation Examples 45 Figure 26 Mechanical Dispenser Applications Using 7874 Series Pulser Totalizer 401 29 eps...

Page 51: ...mitter Metal Divider Plate Barrier No 7859 J Box Explosion Proof Low Voltage Area Orange White 401 30 eps Black 115 Vac Line BLK Metal Conduit V 0 0 0 0 0 14 AWG 7 x 36 Stranded Wires Gas Oil Resistan...

Page 52: ...N NC NC P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 120 VAC INPUT RATING 120 VAC MAX 0 15 AMP MAX GALLONS 769780 008 Pulse Transmitter Metal Divider Plate Barrier No 7859 J Box Explosion Proof Low Voltage...

Page 53: ...System 2 controller and thence to the pulsers see Figure 29 PetroVend 4 conductor shielded cable part no 12 1026 must be used to connect to pulsers or you must run 18 AWG gas oil and fire resistant w...

Page 54: ...e s PC board to the EXTERNAL position Negative terminals not used w SW1 in the EXTERNAL position Common Pulser Hand Flow 12 PetroVend System 2 PV270 Pump Relay Board To Pulsers To Other PetroVend PV27...

Page 55: ...he Micon 200 electronic dispenser head and thence to the pulsers Figure 31 TLS 350 LVDIM Installation Kraus Micon 200 Series Electronic Dispensers Not UL Approved 401 32 eps Blue 18 AWG Volume Pulser...

Page 56: ...Micon 200 Electronic Dispenser Head Yellow 18 AWG Pulser Common Line To Other Micon 200 Electronic Dispenser Heads LVDIM LOW VO LTAG E D IS P E N S E R I N TE R FAC E MODUL E 12 11 10 9 5 6 7 8 1 2 3...

Page 57: ...le in metal conduit Figure 33 LVDIM Installation With GasBoy 9800 Or Tokheim 2600 Series Electronic Dispenser Head 401 33 eps GasBoy 9800 or Tokhiem 2600 Series Electronic Dispenser Head Pulse 1 Red N...

Page 58: ...AG E D ISP E NS E R IN T E R FAC E MODULE 12 11 10 9 5 6 7 8 1 2 3 4 SOURCE INPUT RATING 30 VDC MAX 0 1 AMP MAX 401 5 eps GasBoy 9800 or Tokhiem 2600 Series Electronic Dispenser Head GasBoy 9800 or To...

Page 59: ...For technical support sales or other assistance please visit www veeder com...

Reviews: