POS App Guide
DIM Installation Examples
48
LVDIM Applications
• TLS-350 - Up to 4 single product fueling positions are supported per module, and a maximum of 8 modules (32
fueling positions) per system are supported.
• TLS-450 /TLS-450PLUS- Up to 12 single product fueling positions are supported per module, and a maximum
of 4 modules (48 fueling positions) per system are supported.
PETROVEND SYSTEM 2 CONTROLLER
LVDIM is connected to the PV270 pump relay board (in the System 2 controller) and thence to the pulsers (see
Figure 29).
PetroVend 4-conductor shielded cable (part no. 12-1026) must be used to connect to pulsers; or you must run
#18 AWG gas, oil, and fire-resistant wire in metal conduit (separate from high-voltage wiring) to the pulsers.
Figure 29. TLS-350 LVDIM Installation With PetroVend System 2 Site Controller