  VPS Installation

This manual contains instructions to install a Veeder-Root (In-Station Diagnostic) Vapor Pressure Sensor (VPS) in 

the dispenser vapor return line or in a vapor vent stack enclosure. 

For a VPS sensor that will be direct wired to a TLS console, this manual assumes all preliminary site preparation is 

completed, and that wiring from the console to a VPS intrinsically-safe junction box is in place and meets the 

requirements set out in the appropriate console Site Prep manual.

For wireless VPS sensor installations, follow the steps herein to install the VPS sensor itself, but refer to manual 

577013-964 for installation of, and connection to, the wireless components.

Installation of the VPS on the vapor vent stack is only allowed at facilities equipped with a

“Veeder-Root Vapor Polisher” or “Franklin Fueling System Healy Clean Air Separator.

Contractor Certification Requirements

Veeder-Root requires the following minimum training certifications for contractors who will install and set up the 

equipment discussed in this manual:

All service personel on site must comply with all recommended safety practices identified by OSHA and your employer.
Review and comply with all the safety warnings in this an any related documents, and any other Federal, State, or Local 
requirements

Warranty Registrations

 may only be submitted by selected Distributors.

Veeder-Root Contractor 

Certification Requirements

Installer 

Certification

6

ATG Technician 

Certification

7

VR Vapor Products 

Certification

8

TLS-450PLUS

EVR for CA

Certification

Install

ISD

X

X

X

X

Install PMC

X

X

X

X

Install CCVP

X

X

X

X

Install Wireless ISD/PMC

X

X

X

X

Installation Checkout

2

X

X

X

ATG Startup

3

 / Training

4

 / Service

5

X

X

X

ISD Startup / Training / Service

X

X

PMC Startup / Training / Service

X

X

CCVP Startup / Training / Service

X

X

Wireless ISD/PMC Startup / Training / Service

X

X

Install Pressure Sensor (ATG)

X

X

X

X

Maintain Pressure Sensor (ATG)

X

X

X

Calibrate Pressure Sensor (ATG)

X

X

X

Clear ATG Pressure Sensor Alarm (ATG)

X

X

X

Clear ISD/PMC Alarms (ISD/PMC)

X

X

1

Perform wiring and conduit touting; equipment mounting 

2

Inspect wiring and conduit routing; equipment mounting

3

Turn power on, program and test the systems

4

Provide supervised field experience in service techniques and operations

5

Troubleshoot and provide routing maintenance

6

UST Monitoring Systems – Installer (Level 1)

7

Certified UST Monitoring Technician

8

VR Vapor Products

Summary of Contents for TLS-3 Series

Page 1: ...Manual No 577013 797 Revision P Installation Guide Vapor Pressure Sensor TLS 450PLUS TLS 3XX Consoles...

Page 2: ...signed Bill of Lading BOL to Veeder Root Customer Service at 800 234 5350 3 Veeder Root will file the claim with the carrier and replace the damaged missing product at no charge to the customer Custom...

Page 3: ...stall in Horizontal Access Fitting or Vapor Return Line ISD Installation with Air Flow Meter Below Shear Valve 11 Figure 5 Example VPS Installation Below Vertical Access Fitting or Vapor Return Line I...

Page 4: ...ded safety practices identified by OSHA and your employer Review and comply with all the safety warnings in this an any related documents and any other Federal State or Local requirements Warranty Reg...

Page 5: ...Install Setup Operation Manual TLS 350 For Sites With TLS 450PLUS Consoles 577014 073 TLS 450PLUS Site Prep and Installation Manual 577014 484 Veeder Root ISD For TLS 450PLUS Consoles Install Manual V...

Page 6: ...dress practices not related to physical injury WARNING This product is to be installed and operated in the highly combustible environment of a gasoline dispenser where flammable liquids and explosive...

Page 7: ...ified yellow Gas TFE plumbing tape Intrinsically safe devices must be installed in accordance with Article 504 of the National Electrical Code ANSI NFPA 70 for installation in the United States or Sec...

Page 8: ...S bend 333006 001 10 1 Tube copper 1 4 OD x 8 length 333018 001 11 1 Ball valve 3 way 1 4 576008 649 12 1 Hub conduit liquid tight 1 2 zinc 576010 715 13 3 Conduit clamp 2 steel std duty 514100 478 1...

Page 9: ...m and necessary bolts nuts and washers from the included Universal Sensor Mounting kit Wrap the rubber shim item 10 in Table 1 around the sensor before inserting it into the clamp The VPS sensor must...

Page 10: ...VPS wiring with wire nuts see Figure 6 For Wireless installations skip Steps 11 13 The VPS sensor connects to a TLS RF transmitter not to field wiring from the TLS Console see manual 577013 964 for in...

Page 11: ...enser 2 or 3 common main vapor return line Pressure Sensor Wrap rubber shim from kit around sensor before inserting in clamp Pressure sensing port Cable Vapor return line shear valve Cord grip Base of...

Page 12: ...2 or 3 common main vapor return line Pressure Sensor Wrap rubber shim from kit around sensor before inserting in clamp Pressure sensing port Cable Vapor return line shear valve Cord grip Base of dispe...

Page 13: ...Wrap rubber shim from kit around sensor before inserting in clamp Pressure sensing port Cable Vapor return line shear valve Cord grip Base of dispenser cabinet 797 9 eps Pitch to drain 1 4 vertical p...

Page 14: ...sensor before inserting in clamp Pressure sensing port Pitch to drain 1 4 vertical per 12 horizontal 12 4 11 2 2 2 2 3 2 1 10 OR Seal off customer supplied Conduit to TLS Console Cable Cord grip Flow...

Page 15: ...ng port 3 1 10 Seal off customer supplied Conduit to TLS Console Cable Cable Cord grip Flow Meter and Pressure Sensor wiring can share the same conduit to console Observe polarity Required Y fitting f...

Page 16: ...wn in A bend pak along long length 3 As shown in B firmly squeeze the RED SIDE of the resin forcing it through the center seal and into BLACK SIDE 4 Mix thoroughly to a uniform color by squeezing cont...

Page 17: ...4 Figure 8 Direct Wired VPS Connects to Available TLS 450PLUS USM Module Position Figure 9 Direct Wired VPS Connects to Available TLS 3XX Smart Sensor Interface Module Position For wireless configurat...

Page 18: ...e item 2 in Table 2 such that the VPS cable outlet is facing up and the pressure sensing port tube in the base of the sensor is facing down The symbol on the panel should be facing upward Use the four...

Page 19: ...of the tube up and estimate the length needed to loop from the bottom of the drying tube over to the vent port off center of the VPS Cut the Tygon tubing at the estimated length approximately a foot...

Page 20: ...VPS Installation Vapor Vent Stack Installation Wired VPS 1717 Figure 10 Locating Direct Wired VPS Sensor Enclosure on Vapor Vent Stack...

Page 21: ...VPS Installation Vapor Vent Stack Installation Wired VPS 18 Figure 11 Direct Wired VPS Sensor Installed in Vapor Vent Stack Enclosure...

Page 22: ......

Reviews: