5
Installation
This pumping system requires the following elements:
1.
Discharge Manifold Assembly - Installed below grade (NEC/Class I, Group D, Division I area)
2.
Motor-Pump Unit Assembly - Installed below grade (NEC/Class I, Group D, Division I area)
3.
Control Box/Magnetic Starter
An “all inclusive” name plate will be found attached to the Extracta Head and can be inspected by removing
the manhole cover directly over the pump.
An additional name plate will be found on the control box. It is important to give the model number and serial
number of this pump when corresponding with the factory for any reason.
INSTALLATION SAFETY NOTICES ATTENTION INSTALLER
Read This Important Safety Information Before Beginning Work.
1.
Units should be installed with manholes, or with discharge manifold casting above grade, to allow for ease in
servicing.
Red Jacket line leak detection systems do not function if the submersible pump runs
continuously. Running a pump continuously will cause line leak detection systems to
not function which results in a hazard that can cause damage to property, environment,
resulting in serious injury or death.
2.
Never wire a submersible pump to run continuously at less than minimum flow rate. The units are designed to
operate continuously at or above minimum flow rate, or with an intermittent duty cycle, not to exceed 20 on/off
cycles per hour. Should it be necessary to operate a unit continuously or when the demand is at a rate less
than required per the information below, a bypass pipe should be installed in the piping to allow for continual
product recirculation back into the storage tank. Regulation of the bypass flow back to the tank can be
accomplished by correct sizing of the bypass line or use of a gate valve. The recommended minimum bypass
per unit is shown in Table A.
3.
Red Jacket submersibles are not designed to handle abrasives or foreign particles in the product being
pumped.
4.
Product temperature must never exceed 105°F (41°C) as the submersible motors are equipped with thermal
overload protection. Product temperature higher than 105°F (41°C) may result in tripping of the thermal
overload protector.
Table A.
60 Hz, 208-240, 575 Volt
Two Stage Units
50 Hz 380-415 Volt
Three Stage Units
P200J1-2MB = 15 GPM
P300J17-3HB = 20GPM
P200J4-2MB = 15 GPM
P500J17-3K = 25 GPM
P300J4-2HB = 20 GPM
P300J16-3HB = 20GPM
P500J4-2K = 25 GPM
P500J16-3K = 25 GPM
P200J6-2K = 25 GPM
WARNING