ANZEx CONDITIONS OF CERTIFICATION:
1.
It is a condition of manufacture that each motor be subjected to the routine high
voltage test of clause 6.2 of AS2380.1.
2.
It is a condition of safe use that all submerged turbine pumps, manifolds and
associated equipment be installed in accordance with the manufacture
r
’s
Installation, Operation and Service Manuals supplied
3.
It is a condition of safe use that all installations must provide reliable electrical
connection between the pump motor, frame, pipe, manifold or junction box and
the tank structure for both electrical protection and equipotential bonding.
4.
It is a condition of safe use that, where terminal boxes are used for termination of
the cables from the motor and the supply source, they shall be Australian certified
for use in Gas Group IIA and Zone I hazardous areas.
5.
It is a condition of safe use that where a differential pressure switch or transducer
is installed, each must be capable of ensuring that the nominated temperature
classification is not exceeded.