Vector printer Installation and Commissioning Manual
.
7
Print options cont’d
4. PRINT DEVICE PARAMETERS. Prints device information in the form
001 OPT ZONE 01 G****
address type
zone groups
SMOKE
DETECTOR
GROUND
FLOOR
text
message.
This print will report all devices assigned to the panel selected.
With one option above chosen, select the required panel and loop number on the network by scroll-
ing the panel number from 00 to 15, and scrolling the loop number 1 - 4. The selection should default
to the local panel. Press button 5 to print . Press menu button to exit.
Other printouts
The printer will print all alarms and faults (if selected) in real time in the form:-
**********FIRE**********
FIRE PANEL 00 LOOP 01 ZONE 04
TYPE MAN ADDRESS 020 22:48 04/01
MANUAL CALL POINT TEXT MESSAGE HERE
Test mode .
When test mode is used the printer will record the devices tested:-
TEST ADD 020 MAN ZONE 04 22:43 04/01
TEST ADD 019 OPT ZONE 04 22:41 04/01
Maintenance check. When this engineering mode is used, the printer will record devices with an ana-
log value above the threshold selected, They are printed as the display is manually scrolled.
Maintenance P00 OPT Ana 34
Maintenance P00 ION Ana 32
P00 refers to the panel number , Ana 34 refers to the analog value returned by the device.
Troubleshooting
The printer will not print :-
is there paper available, is the printer address correct. Are dil switch op-
tions set correctly. Is panel V4.0 or above, is paper correctly installed.?
(i.e. coating upwards).
Comms disconnected:-
Is PCB connected correctly.
‘Printer supply’ led out:-
Check supply fuse