Vector printer     Installation and Commissioning Manual

.                                                                                                

7

 

Print options cont’d 

 
 

4. PRINT DEVICE PARAMETERS. Prints device information in the form 
                                          

 

 001 OPT                                    ZONE  01  G**** 

                                           

 

address type 

 

 

 zone          groups   

      SMOKE 

DETECTOR 

GROUND 

FLOOR 

      text 

message. 

 

This print will report all devices assigned to the panel selected. 
 
With one option above chosen, select the required panel and loop number on the network  by scroll-
ing the panel number from 00 to 15, and scrolling the loop number 1 - 4. The selection should default 
to the local panel. Press button 5 to print . Press menu button to exit. 

 
 

Other printouts 

 

The printer will print all  alarms and faults (if selected) in real  time  in the form:- 

 

                          **********FIRE********** 
 

 

FIRE  PANEL 00      LOOP 01      ZONE 04 

 

 

TYPE MAN     ADDRESS 020                     22:48   04/01 

 

 

MANUAL CALL POINT  TEXT MESSAGE HERE 

 
 

Test mode .  

When test mode is used the printer will record the devices tested:- 

 
                         

TEST       ADD 020  MAN  ZONE  04   22:43  04/01 

 

 

 

TEST      ADD 019   OPT  ZONE  04  22:41 04/01 

 
Maintenance check. When this engineering mode is used, the printer will record devices with an ana-
log value above the threshold selected, They are printed as the display is manually scrolled. 

 
                   

Maintenance P00  OPT Ana 34 

 

 

  Maintenance P00  ION   Ana 32 

P00 refers to the panel number , Ana 34 refers to the analog value returned by the device. 
 
 

 
Troubleshooting 

 

The printer will not print :- 

is there paper available, is the printer address correct. Are dil switch op-

tions set correctly. Is panel V4.0 or above, is paper correctly installed.? 
(i.e. coating upwards). 

 

Comms disconnected:-   

Is PCB connected correctly. 

 

‘Printer supply’ led out:-

     Check supply fuse 

 

 

 

 

 

 

Summary of Contents for V4.1

Page 1: ...Network Printer V4 1 and above Installation Commissioning Manual MVEC 03 Issue 3 0 July 2008 ...

Page 2: ......

Page 3: ... Page Introduction 3 ESD Precaution 3 Installation Retro fit 4 Replacing the paper roll 4 Powering up the printer 5 Printer indications 5 Paper feed 5 Print options 5 Other Printouts 6 Trouble shooting 6 Drawing S1620 Connection Diagram 7 Technical Specification 8 ...

Page 4: ... used to log engineer tests and produce a maintenance report The printer is complete with a paper feed button and paper out indicator Two printer options are available via an on board dual in line switch 1 system wide or local printing 2 suppress fault printing or print all faults ESD Precaution Electronic components are vulnerable to damage by Electrostatic Discharges ESD An ESD wrist strap suita...

Page 5: ...eplaced or retro fitted to the control panel Firstly remove the existing control panel lid Disconnect the key switch and earth link cables from the back box Once removed lift away the lid and fit the new lid in a similar manner Terminate cables in line with the Drawing S1620 see back of manual Replacing the paper roll The printer requires special thermal paper which can be obtained from the suppli...

Page 6: ...ot being received by the printer the message will read Comms disconnected Network wide events will be printed but device text is only printed for the local panel A Network Wide printer will not print individual device text messages Indications Printer Supply Green light will be illuminated when power is at the printer interface No paper A yellow LED on the printer mechanism will pulse if paper is ...

Page 7: ...L 00 LOOP 01 ZONE 04 TYPE MAN ADDRESS 020 22 48 04 01 MANUAL CALL POINT TEXT MESSAGE HERE Test mode When test mode is used the printer will record the devices tested TEST ADD 020 MAN ZONE 04 22 43 04 01 TEST ADD 019 OPT ZONE 04 22 41 04 01 Maintenance check When this engineering mode is used the printer will record devices with an ana log value above the threshold selected They are printed as the ...

Page 8: ...Vector printer Installation and Commissioning Manual 8 Drawing S1620 showing printer connection details ...

Page 9: ...scent Power consumption 500 milliamps peak during printing Printing method High speed thermal Paper Thermal coated 58mm x 25 metre roll THM582512 Signalling CAN 2 0 data bus Max 16 printers per network Dimensions lid mount 90mm x 60mm x20mm pod on door front Dimensions stand alone 320mm high x 160mm wide x 85mm deep Weight 2 4 Kg Cabling FP200 or equivalent maximum capacitance 1µF maximum inductan...

Page 10: ......

Reviews: