INSTRUCTIONS 

 

Powering up the printer

 

 

Once all the settings are checked the cabling connected and the paper roll installed, the printer 
may be powered up (along with the control panel) . The printer will record a message:- 
 

Vector M system (or local)  Printer V4.0 
Panel xx 
Fault printing disabled 

 
This message reflects the switch settings. 
 
In order to reduce traffic on the communications bus, the text messages reside in a memory on 
the printer interface. These are automatically updated by the system.  

 

After a short time the printer may record a message saying :- 
 

Device names updated, panel xx.  

 
This message will be printed each time a name is changed in any panel on the network either by 
download or manual editing. If communications are not being received by the printer the message 
will read :- 
 

Comms disconnected   

 

Network wide events will be printed, but device text is only printed for the local panel. A ’Network 
Wide’ printer will not print individual device text messages. 

 
  

Indications 
 

Printer Supply

 

Green light will be illuminated when power is at the printer interface. 

 

No paper

 

A yellow LED on the printer mechanism will pulse if paper is not present in the printer rollers.  
 

NOTE:- 

the mechanism will not attempt to print if  paper is not fitted.  

  

Paper feed button 

Pressing this button will advance the paper. . 

 

Print options 

 
In the Vector control panel menu, item no 7. PRINT OPTIONS, four options are available:- 

 

1. PRINT ALARM LOG. Prints all  alarms and evacuations in the form,                                   
 

 

 

 

FIRE ADD 013 OPT ZONE 03   11:39  13/04.

  

 

 

 

 

alarm    address  type   zone              time    date dd/mm 

2

. PRINT FAULT LOG . Prints all faults in the form. 

 

 

 

 

UNASSIGNED  ADD 013 OPT    11:39  13/04.  

 

 

 

 

fault                      address   type     time     date dd/mm 

3.PRINT USER LOG. Prints type, time and date of user actions

 
  

Summary of Contents for V4.1

Page 1: ...Network Printer V4 1 and above Installation Commissioning Manual MVEC 03 Issue 3 0 July 2008 ...

Page 2: ......

Page 3: ... Page Introduction 3 ESD Precaution 3 Installation Retro fit 4 Replacing the paper roll 4 Powering up the printer 5 Printer indications 5 Paper feed 5 Print options 5 Other Printouts 6 Trouble shooting 6 Drawing S1620 Connection Diagram 7 Technical Specification 8 ...

Page 4: ... used to log engineer tests and produce a maintenance report The printer is complete with a paper feed button and paper out indicator Two printer options are available via an on board dual in line switch 1 system wide or local printing 2 suppress fault printing or print all faults ESD Precaution Electronic components are vulnerable to damage by Electrostatic Discharges ESD An ESD wrist strap suita...

Page 5: ...eplaced or retro fitted to the control panel Firstly remove the existing control panel lid Disconnect the key switch and earth link cables from the back box Once removed lift away the lid and fit the new lid in a similar manner Terminate cables in line with the Drawing S1620 see back of manual Replacing the paper roll The printer requires special thermal paper which can be obtained from the suppli...

Page 6: ...ot being received by the printer the message will read Comms disconnected Network wide events will be printed but device text is only printed for the local panel A Network Wide printer will not print individual device text messages Indications Printer Supply Green light will be illuminated when power is at the printer interface No paper A yellow LED on the printer mechanism will pulse if paper is ...

Page 7: ...L 00 LOOP 01 ZONE 04 TYPE MAN ADDRESS 020 22 48 04 01 MANUAL CALL POINT TEXT MESSAGE HERE Test mode When test mode is used the printer will record the devices tested TEST ADD 020 MAN ZONE 04 22 43 04 01 TEST ADD 019 OPT ZONE 04 22 41 04 01 Maintenance check When this engineering mode is used the printer will record devices with an ana log value above the threshold selected They are printed as the ...

Page 8: ...Vector printer Installation and Commissioning Manual 8 Drawing S1620 showing printer connection details ...

Page 9: ...scent Power consumption 500 milliamps peak during printing Printing method High speed thermal Paper Thermal coated 58mm x 25 metre roll THM582512 Signalling CAN 2 0 data bus Max 16 printers per network Dimensions lid mount 90mm x 60mm x20mm pod on door front Dimensions stand alone 320mm high x 160mm wide x 85mm deep Weight 2 4 Kg Cabling FP200 or equivalent maximum capacitance 1µF maximum inductan...

Page 10: ......

Reviews: