TRA-F12x-A
R
UNTIME
D
ATA
Doc: 70-00-0792B V1.3, 20220830
© Vector Controls GmbH, Switzerland
Page 31-34
Subject to change without notice
www.vectorcontrols.com
V
ECTOR
Data/Addr Description
Data type / value
Default R/W
1203
Outdoor temperature Modbus
Multiplier: 10; Integer (signed)
-
20.0…60.0 °C
-100.0 (= 0xFC18) = no valid temperature
received yet
none
R/
W
1204
RT1 digital input
0 = OFF
1 = ON
-1 = none (Temperature input)
none
R
1205
RT2 digital input
0 = OFF
1 = ON
-1 = none (Temperature input)
none
R
1300
Heating control output
0…100 %
none
R
1301
Cooling control output
0…100 %
none
R