TRA-F12x-A
C
ONFIGURATION
Doc: 70-00-0792B V1.3, 20220830
© Vector Controls GmbH, Switzerland
Page 29-34
Subject to change without notice
www.vectorcontrols.com
V
ECTOR
5.10
Load and store default settings
5.10.1
With user interface
Press up and down for minimum 3 seconds to enter the password protected default settings.
Enter the default settings with CODE 245. Choose between default TRA-F12x-
A “dEF” and OEM “OE” configuration copy
menu. Navigate with Up ( ), Down ( ), Enter ( ) and Return Buttons ( , ).
After a load or store action the small digits show “Good” and the default settings menu is closed.
Large Digits
Small Digits
Action with Enter Button ( )
dEF
no
LOAd
No action
Load default TRA-F12x-A configuration (as described in this manual)
OE
no
LOAd
SAVE
No action
Load default OEM configuration
Save default OEM configuration
5.10.2
With Modbus
Via Modbus the default settings can be accessed by writing 2 registers (with function code 0x16 write multiple registers)
to data address 37. After a load or store command via Modbus,
the small digits show “Good” and the large digits show
“CPy” on the
user interface.
Addr
Description
Required Qty
Data type
R/W
37
Default configuration type
2 registers
(function code
0x16: write multiple
registers)
0 = Default TRA-F12x-A configuration
1 = OEM default configuration
W
38
Action for default configuration
0 = No action
1 = Load config. as defined with address 37
2 = Save actual config. to OEM default
(only valid when address 37 = 1)
W