TLC3-FCR-2T-U Engineering Manual

 

 

Doc: 70-00-0203, V3.0 Date: 20121119 

© Vector Controls GmbH, Switzerland

mailto:[email protected]

 

Page 1 

Subject to alteration 

TLC3-FCR-2T-U 
Intelligent Fan Coilcontroller 

Features 

 

The PWM and 3-point floating control option reduces room 

temperature fluctuations and energy consumption 

 

Low power energy consumption: < 1W per unit 

 

Temperature control for 2- and 4-pipe fan coil systems.  

 

Automatic fan control for three stage fans.  

 

Cost saving option with Economy functionality and set point 

limitations 

 

Control for single stage heating, cooling and fan only operation 

modes 

 

Password protected programmable user and control parameters 

o

 

Setpoint range limitation 

o

 

Access control for setpoints, fan speeds and mode change 

o

 

Access control for heat/cool change and time programs 

o

 

Select your display contents 

o

 

Selectable behavior after return from power failure 

 

Temperature display in Celsius or Fahrenheit 

Deluxe Version: 

 

Clock and time schedule functions with power failure protection 

 

Blue backlight for LCD 

 

Infrared remote controller option:  

With special features for Boost and delayed switching on or off 

Applications 

 

Air Only Systems:  

o

 

Constant Air Volume systems with three stage fans for single or dual duct systems 

 

Air/Water Systems:  

o

 

Fan Coil units for 2-pipe or 4-pipe systems  

o

 

radiator control, chilled ceiling 

 

Simple individual room control for hotel rooms, meeting rooms, etc.  

 

PWM or On-Off-Control of 2 spring return valves or 3-point on-off or floating control of one 3-point valve.  

General Description 

The TLC3-FCR-2T is a stand-alone electronic fan coil controller with one control loop. The TLC3-FCR-2 features 1 NTC 

temperature sensor input and five binary outputs. Three outputs control a fan with low, medium and high fan speeds. 

Two binary outputs may be used to control either two spring return or thermal valves or one three point floating valve.  
A detailed parameterization is possible with the use of a simple configuration routine. The TLC3-FCR-2-U can be 

configured using the standard operation terminal. No special tools or software is required.  

Ordering 

Item Name 

Item code 

Variant 

Power 

Features 

TLC3-FCR-2R-U-24 

TLC3-FCR-2R-U-24-W01 

40-10 0140 

40-10 0140-01 

Standard 

Cooling only 

24VAC/DC 

Fan coil controller with:  
1 TI int 

3 DO (Relay) Fan control 

2 DO (Relay) Binary valve control 

TLC3-FCR-2R-U-D-24 

TLC3-FCR-2R-U-D-24-W01 

40-10 0145 

40-10 0145-01 

Deluxe 

Cooling only  24VAC/DC 

TLC3-FCR-2T-U-120 

TLC3-FCR-2T-U-120-W01 

40-10 0150 

40-10 0150-01 

Standard 

Cooling only 

120VAC 

Fan coil controller with:  
1 TI int 

3 DO (Relay) Fan control 

2 DO (TRIAC) Binary valve control 

TLC3-FCR-2T-U-D-120 

TLC3-FCR-2T-U-D-120-W01 

40-10 0155 

40-10 0155-01 

Standard 

Cooling only 

120VAC 

TLC3-FCR-2T-U-230 

TLC3-FCR-2T-U-230-W01 

40-10 0120 

40-10 0120-01 

Standard 

Cooling only  230VAC 

TLC3-FCR-2T-U-D-230 

TLC3-FCR-2T-U-D-230-W01 

40-10 0121 

40-10 0121-01 

Deluxe 

Cooling only 

230VAC 

Selection of valve actuators and fans 

Binary auxiliary devices: E.g. fans and on/off valves.  Observe switching power as detailed under technical 

specifications! Do not connect more than one fan coil unit to one controller. 

Summary of Contents for TLC3-FCR-2T-U

Page 1: ...ves or 3 point on off or floating control of one 3 point valve General Description The TLC3 FCR 2T is a stand alone electronic fan coil controller with one control loop The TLC3 FCR 2 features 1 NTC t...

Page 2: ...idity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004...

Page 3: ...unting plate 3 Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front...

Page 4: ...on to operate accordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode w...

Page 5: ...ptions d1 7 d1 6 d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switch...

Page 6: ...the temperature loop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan s...

Page 7: ...UP 01 Enable change of set points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 0...

Page 8: ...FC 05 Switching Span Heating Setting this value to 0 disables the auto fan speed function in heating mode 0 10 0 C 20 0 F 1 5 C 3 F FC 06 Switching Span Cooling Setting this value to 0 disables the a...

Page 9: ...nary output DO4 open DO5 close 2 3 point floating output DO4 open DO5 close 0 2 0 Binary PWM FC 17 Running Time in 3 point mode 0 255 s 90 s FC 18 PWM cycle timeheating 0 disables PWM mode 0 100 min 0...

Page 10: ...TLC3 FCR 2T U Engineering Manual Doc 70 00 0203 V3 0 Date 20121119 Vector Controls GmbH Switzerlandmailto info vectorcontrols com Page 10 Subject to alteration Notes...