Vector TLC3-FCR-2R-24 Engineering Manual Download Page 9

 

 

TLC3-FCR-2T Engineering Manual

 

 

Doc: 70-00-0202, V3.0 Date: 20121119 

© Vector Controls GmbH, Switzerland 

Page 9 

Subject to alteration 

Control Configuration for PWM – 3-point floating mode 

FC 14 

P – band heating X

PH

 

0-10.0°C (20.0°F) 

2.0°C (4.0°F) 

FC 15 

P – band cooling X

PC

 

0-10.0°C (20.0°F) 

2.0°C (4.0°F) 

 

Proportional control(P-band)  

The proportional control function calculates the output based on the difference between setpoint and measured 

value. The proportional band (P-band) defines the difference between setpoint and measured value which will 

result in a 100% output. Setting the proportional band to 0 disables proportional control. 

 

Output configuration 

FC 16 

Output setting, Binary, PWM or 3-point:  
0 = Binary or PWM (DO4 Heating, DO5 Cooling) 

1 = 3-point binary output (DO4 open, DO5 close) 

2 = 3-point floating output (DO4 open, DO5 close) 

0…2 

Binary / PWM 

FC 17 

Running Time in 3-point mode 

0…255 s 

90 s 

FC 18 

PWM cycle timeheating, 0 disables PWM mode 

0…100 min 

FC 19 

PWM cycle time cooling, 0 disables PWM mode 

0…100 min 

 

3-point floating:  

For floating point outputs the running time of the actuator used needs to be specified with FC17. Running time is 

defined as the time required for the actuator to run from fully open to fully closed and vice versa. Actuators with a 

fixed running time are recommended. Once fully open or fully closed the running time for the actuator is extended 

for a full run-time cycle. This will allow the actuator position to be synchronized in case it has been moved during 

off time or an actuator with variable running time was used.

 

 

Pulse With Modulation (PWM) 

In PWM mode the digital output will be switched on/off once per cycle. The on and off times are calculated 

according to the control sequence.

 

 

 

Summary of Contents for TLC3-FCR-2R-24

Page 1: ...idual room control for hotel rooms meeting rooms etc PWM or On Off Control of 2 spring return valves or 3 point on off or floating control of one 3 point valve General Description The TLC3 FCR 2T is a...

Page 2: ...itions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Pro...

Page 3: ...Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the...

Page 4: ...cordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once...

Page 5: ...d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One ba...

Page 6: ...loop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be...

Page 7: ...nge of set points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access t...

Page 8: ...Span Heating Setting this value to 0 disables the auto fan speed function in heating mode 0 10 0 C 20 0 F 1 5 C 3 F FC 06 Switching Span Cooling Setting this value to 0 disables the auto fan speed fu...

Page 9: ...open DO5 close 2 3 point floating output DO4 open DO5 close 0 2 0 Binary PWM FC 17 Running Time in 3 point mode 0 255 s 90 s FC 18 PWM cycle timeheating 0 disables PWM mode 0 100 min 0 FC 19 PWM cycle...

Page 10: ...TLC3 FCR 2T Engineering Manual Doc 70 00 0202 V3 0 Date 20121119 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes...

Reviews: