Vector TEF Manual Download Page 7

 

PI Thermostat TEF

 

V1.3a, 20100504 

© Vector Controls GmbH, Switzerland 

Page 7/8 

Subject to alteration

 

Setting of control parameters 

Warning! Only experts should change these settings! 

The password for the expert user is 14. See setting for user parameters for login details.  

Expert Description 

Display  Standard 

E0 

Actuator running time Opening, 10…990 seconds 

01 - 99 

10 

E1 

Actuator running time Closing, 10…990 seconds 

01 – 99 

10 

E2 Control 

mode 

0 = PI control, 1 =On/Off control 

0, 1 

E3 

P – Band / Hysteresis Temperature loop, Select the 
accuracy of the temperature loop in degrees Kelvin.  

0.5…8.0 2.0 

E4 

Maximum of I part of Analog Loop, Limits the influence of 

the integral part on the output signal. 0 disables the I part 

0.0…A0 (100) 

0.0 

E5 

Tn, Reset time of Analog loop integral, 0.5 - 30 min 

0.5…30 

02 

E6 

For on/off control only: 2 pipe or 4 pipe system 
0 = 2 pipe system, 1 = 4 pipe system 

0, 1 

E7 

For 2-pipe systems only: Enable Fan Control 
0 = No Fan control, 1 = Fan Control 

0, 1 

E8 

Reversing Difference in percentage of actuator position 

00…A0 (100) 

10 

E9 

Switching Difference in percentage of actuator position 

00…A0 (100) 

Mechanical Design 

The unit consists of three parts:  

 

The base unit, which contains the terminal connecters, temperature sensors and control logic 

 

The front plate, which holds the buttons 

 

The base plate, to ease installation  

Mounting location 

 

On an easy accessible interior wall, approx.  
1.5 m above the floor in an area of average temperature. 

 

Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting electrical 

equipment.  

 

Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

 

Location of mounting is less critical if external temperature sensors are used.  

Installation 

1.

 

Install the mounting plate on the wall box. The type 

of screws required depends on the wall box. For 

Chinese standard M4x25 screws are most suitable. 
The mounting plate provides holes for most 

international standards. Horizontal distance of 

mounting screws ranges from 35 to 65 mm; vertical 
distances are 58 to 85 mm. 

2.

 

On the upper side of the controller, there are two 

clips. Press them inside using a small screwdriver. 

3.

 

Separate the front plate of the controller with the 

base by opening it carefully. Unplug the connector 

from the button. 

4.

 

Connect the wirings as shown in the diagram below. 
Pay attention to follow local guidelines regarding 

insulation and wire sizes. 

5.

 

Connect the main body to the mounting plate by 
holding it in place and inserting the two small 

screws that are part of the package in the upper left 

and lower right corner. 

6.

 

Reconnect the plug of the button and press the 

front plate into place. Insert the lower part first and 

then press down the upper part until hearing a click. 

Summary of Contents for TEF

Page 1: ...l Radiator or floor heating cooling ceiling General Description The TEF is a stand alone electronic temperature controller with one PI control loop It features 1 PI sequence and 2 binary sequences The...

Page 2: ...midity To IEC 721 3 3 class 3 K5 0 50 C 95 r h Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 95 r h...

Page 3: ...ycle after resuming of power supply A reset is necessary if the unit was in operation during power failure The actuator position would then be lost and has to be regenerated The controller assumes it...

Page 4: ...arameters can be changed as follows 1 Press LEFT and RIGHT button together for three seconds The display will indicate PP and both status LED s are blinking in orange 2 Select a password using UP or D...

Page 5: ...well the heating setpoint The factory setting for the dead zone span is 1K T Room Temperature wH Setpoint Heating Xp E3 Proportional Band wC Setpoint Cooling YT Output signal of temperature loop XDZ P...

Page 6: ...ode therefore changes as well the heating setpoint The factory setting for the dead zone span is 1K T Room Temperature wH Setpoint Heating HRC E3 Hysteresis Heating Cooling wC Setpoint Cooling WH XDZ...

Page 7: ...the buttons The base plate to ease installation Mounting location On an easy accessible interior wall approx 1 5 m above the floor in an area of average temperature Avoid direct sunlight or other hea...

Page 8: ...4 Power Supply Ground 5 Power supply 24 V AC DC 6 External temperature Sensor 7 External temperature Sensor In order to activate External sensor RT must be cut T EF External temperature sensor GND 24...

Reviews: