Vector TEF Manual Download Page 5

 

PI Thermostat TEF

 

V1.3a, 20100504 

© Vector Controls GmbH, Switzerland 

Page 5/8 

Subject to alteration

 

Control Function 

Temperature Control Mode: PI Control E2=0 

The controller reads the temperature either by using its integrated temperature sensor or by using an external 

sensor. The controller maintains the temperature set point by calculating the position of the actuator using a 3-

point modulating signal. The on/off actuator is positioned based on its opening and closing time. The 
temperature is controlled using a PI control function. If both P and I parts are enabled, they will be added 

together to calculate the output position. Following control parameters decide the function of the PI loop:  

 

E3: P-band in °K. The p-band corresponds to the temperature difference of current value to setpoint, 
which is required for fully opening the output.  

 

E4: A large I part increases the swinging tendency of the control loop. Limiting the integral part may 

reduce this tendency. The I-part is disabled if 0 is selected. 

 

E5: Tn, Reset time of Analog loop integral. Tn is the time needed for the integral to run from 0 to 100%. 

The range is 0.5 - 30 min. The setting very much depends on the application it is used for. For 

temperature control of a medium sized room, a setting of 5 minutes should be appropriate. 

 

P5: Dead Zone Span. The cooling setpoint W

C

 consists of the heating setpoint and the dead zone span. 

Changing the cooling setpoint therefore changes as well the heating setpoint. The factory setting for the 

dead zone span is 1K. 

 
 

 

 
 

 

 

 
 

 
 
T Room 

Temperature 

w

H

 Setpoint Heating 

Xp 

E3: Proportional Band 

w

Setpoint Cooling 

Y

T

 

Output signal of temperature loop 

X

DZ

  P5: Dead Zone Span 

Tn 

E5: Integral Reset Time 

Switching frequency 

The TEF works with two digital outputs to modulate a floating actuator. The position of the actuator is calculated 

with above described PI algorithm. The controller moves the actuator to the calculated position by either 

opening or closing the actuator. The actuator should not be moved for every little change in position, since this 
would reduce the lifetime of the actuator. We differentiate if we are moving the actuator in the same direction 

as the previous move or if we reverse direction.  

 

E7: Switching difference: For example the last actuator movement was opening and we open again. The 
actuator will only move, if the difference to the current actuator position is larger than this parameter. 

 

E6: Reversing difference: For example the last actuator movement was opening and we want to close 

now. The actuator will only move, if the difference to the current actuator position is larger than this 
parameter.  

Below are examples of switching and reversing difference after the actuator has been opening on its 

previous move.    

 
 

 

 
 

 

 
 

 

X

T

 

Calculated actuator position 

RD  E6: Reversing Difference 

 

 

Y

T

 

Actual actuator position 

Opening up to step 1 

SD 

E7: Switching Difference 

Actuator acting point 

Y

T

 [%] 

100

0

SD 

Switching Difference 

X

T

[%] 

Y

T

 [%] 

100

0

RD 

Reversing Difference 

X

T

[%] 

Y

T

 [%] 

100

0

Xp 

W

H

 

Xp 

W

C

 

Heating Mode   P Control Part  Cooling Mode 

T [°C] 

Y

T

 [%] 

100

0

Tn 

W

H/C

 

I Control Part 

t [min] 

X

DZ

 

Summary of Contents for TEF

Page 1: ...l Radiator or floor heating cooling ceiling General Description The TEF is a stand alone electronic temperature controller with one PI control loop It features 1 PI sequence and 2 binary sequences The...

Page 2: ...midity To IEC 721 3 3 class 3 K5 0 50 C 95 r h Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 95 r h...

Page 3: ...ycle after resuming of power supply A reset is necessary if the unit was in operation during power failure The actuator position would then be lost and has to be regenerated The controller assumes it...

Page 4: ...arameters can be changed as follows 1 Press LEFT and RIGHT button together for three seconds The display will indicate PP and both status LED s are blinking in orange 2 Select a password using UP or D...

Page 5: ...well the heating setpoint The factory setting for the dead zone span is 1K T Room Temperature wH Setpoint Heating Xp E3 Proportional Band wC Setpoint Cooling YT Output signal of temperature loop XDZ P...

Page 6: ...ode therefore changes as well the heating setpoint The factory setting for the dead zone span is 1K T Room Temperature wH Setpoint Heating HRC E3 Hysteresis Heating Cooling wC Setpoint Cooling WH XDZ...

Page 7: ...the buttons The base plate to ease installation Mounting location On an easy accessible interior wall approx 1 5 m above the floor in an area of average temperature Avoid direct sunlight or other hea...

Page 8: ...4 Power Supply Ground 5 Power supply 24 V AC DC 6 External temperature Sensor 7 External temperature Sensor In order to activate External sensor RT must be cut T EF External temperature sensor GND 24...

Reviews: