TEF 
PI Controller and Thermostat 

 

 

 

Features 

 

Controller: Floating point temperature controller and positioner 

 

On/Off thermostat for 4-pipe or 2-pipe systems with fan function.  

 

Temperature control depending on room or return air temperature 

 

Integrated room temperature sensor 

 

Programmable user and control parameters 

 

Minimum, maximum set point limitation 

 

Enable/Disable change of set points and heating/cooling changeover 

 

Temperature display in Celsius or Fahrenheit  

 

Selectable Frost protection 

 

Operating Voltage 24V 

 

Applications 

 

Individual PI-control of the temperature in rooms that are heated or cooled with 2-pipe systems or 4-

pipe systems using spring return fan coil valves. 

 

Cost efficient control of pressure dependent VAV units. 

 

Positioning of an on/off actuator by using the running time of the actuator 

 

Controlling the temperature output of a simple air-handling unit with one heating or cooling coil. 

 

Radiator or floor heating, cooling ceiling. 

 

General Description 

The TEF is a stand-alone electronic temperature controller with one PI control loop. It features 1 PI sequence 

and 2 binary sequences. The TEF features 1 NTC temperature sensor input. One additional function is the 
manual positioning of a floating actuator.  
The TEF features 2 binary outputs (Relays). A detailed parameterization is possible with the use of a simple 

configuration routine. The TEF can be configured using the standard operation terminal. No special tools or 
software is required.  

Ordering 

Item Name 

Description/Option 

TEF 

Compact PI controller 1 TI internal & external, 2 DO (Relays)  

TEM 

Compact PI controller 1AI, 1 TI int & ext, 1 AO  

Selection of actuators and sensors 

Temperature Sensors: Use only our approved NTC sensors to achieve maximum accuracy.  Recommended is 
SDA-Tn10-20 as Duct sensor, SRA-Tn10 as Room sensor and SPA-Tn10-10 as immersion sensor.  
Floating Actuators: Any actuators with less than 250 VAC, 100W are acceptable. Actuators with constant 
running time are preferred for optimum functionality. 
Binary auxiliary devices: E.g. pumps, fans, on/off valves, humidifiers, etc.  Do not directly connect devices that 

exceed 250 VAC, 100W. 
 

Summary of Contents for TEF

Page 1: ...l Radiator or floor heating cooling ceiling General Description The TEF is a stand alone electronic temperature controller with one PI control loop It features 1 PI sequence and 2 binary sequences The...

Page 2: ...midity To IEC 721 3 3 class 3 K5 0 50 C 95 r h Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 95 r h...

Page 3: ...ycle after resuming of power supply A reset is necessary if the unit was in operation during power failure The actuator position would then be lost and has to be regenerated The controller assumes it...

Page 4: ...arameters can be changed as follows 1 Press LEFT and RIGHT button together for three seconds The display will indicate PP and both status LED s are blinking in orange 2 Select a password using UP or D...

Page 5: ...well the heating setpoint The factory setting for the dead zone span is 1K T Room Temperature wH Setpoint Heating Xp E3 Proportional Band wC Setpoint Cooling YT Output signal of temperature loop XDZ P...

Page 6: ...ode therefore changes as well the heating setpoint The factory setting for the dead zone span is 1K T Room Temperature wH Setpoint Heating HRC E3 Hysteresis Heating Cooling wC Setpoint Cooling WH XDZ...

Page 7: ...the buttons The base plate to ease installation Mounting location On an easy accessible interior wall approx 1 5 m above the floor in an area of average temperature Avoid direct sunlight or other hea...

Page 8: ...4 Power Supply Ground 5 Power supply 24 V AC DC 6 External temperature Sensor 7 External temperature Sensor In order to activate External sensor RT must be cut T EF External temperature sensor GND 24...

Reviews: