Output configuration
Parameter Description
Range
Default
CP 12
Manual Override Mode:
Allows manual control of the floating outputs for using the
controller as positioner or during commissioning.
ON, OFF
OFF
CP 13
Running time FO1 (TCY-FT4 = heating output)
The total time it takes for the actuator to run from fully open
to fully closed or from fully closed to fully open
0-255s
90s
CP 14
Minimum running time FO1 (TCY-FT4 = heating output)
The minimum time the output runs once it starts. This setting
prevents frequent switches with very short running times.
0-255s
3s
CP 15
Running time FO2 (TCY-FT4 = cooling output)
The total time it takes for the actuator to run from fully open
to fully closed or from fully closed to fully open
0-255s
90s
CP 16
Minimum running time FO2 (TCY-FT4 = cooling output)
The minimum time the output runs once it starts. This setting
prevents frequent switches with very short running times.
0-255s
3s
CP 17
Maximum Output in Economy (unoccupied) Mode
Reduces the load on the system when is the space is
unoccupied.
0 – 100 %
50%