Wiring and Connection 

 

 

 

For jumper settings see section 

Output signal configuration

 on page 

5. 

Mounting location 

 

On a flat, easily accessible inner wall 

 

The following installation locations should be avoided: 

o

 

Protect from direct exposure to sunlight 

o

 

Do not install near heat sources, e.g., radiators or other heat-generating devices 

o

 

Areas with poor air circulation and niches, e.g., behind doors or shelves 

o

 

Outside walls insufficiently insulated 

o

 

In the direct influence area of ventilation openings and fans 

 

Mounting instruction 

 

 

See SRC-C1T1 installation sheet no. 70-000809 (

www.vectorcontrols.com

). 

 

Dimension mm (inch)  

 

 

 

 

1 2 3 4

C

NC

NO

V+ 

AC 24 V 50-60 Hz, DC +24 V ± 10% 

GND 

AC 0 V, DC 0 V 

AO1 

CO2, DC 0(2)...10 V 

AO2 

Temperature, DC 0(2)...10 V 

NC 

 

CO2, 48 VAC, 30 VDC, 1 A max  

Off = CO2 low level (green LED) 

On = CO2 high level (red LED) 


NO 

 

Summary of Contents for SRC-C1T1

Page 1: ...rs and if required by a programming module Standard signal ranges are 0 10 VDC and 2 10 VDC Other ranges can be defined by using the external display and programming module OPA S For OPA S usage see s...

Page 2: ...rt applications It is not a safety device Where a device failure could endanger human life and property it is the responsibility of the client installer and system designer to add additional safety de...

Page 3: ...ensation to stabilize after power up Signal outputs Analog outputs Output signal Resolution Maximum load DC 0 10 V or DC 2 10 V 10 bit 9 7 mV Voltage signal 1k Relays output Insulation strength betwee...

Page 4: ...t exposure to sunlight o Do not install near heat sources e g radiators or other heat generating devices o Areas with poor air circulation and niches e g behind doors or shelves o Outside walls insuff...

Page 5: ...ified with output parameter OP 01 and OP 02 is left at the default value of 0 100 With any other setting the position of JP2 has no influence and the signal range defined with the output parameters ap...

Page 6: ...calibration default 1 Calibrate to gas 0 ppm 2 Calibrate to fresh air 400 ppm 0 2 0 1 Sample interval 1 sec 2 Changing this parameter affects the control of the air quality LEDs or relay as follows Ai...

Page 7: ...ecute 400 ppm calibration see section Calibration on page 8 If error cannot be removed by calibrating the sensor replace product Use the CO2 Transmitter as P Controller The CO2 transmitter may be conv...

Page 8: ...ion Once the calibration has been executed the status LED will show constant RED and the green air quality led will blink for 10s if successful If calibration is not successful no stability of concent...

Page 9: ...SRC C1T1 CO2 TEMPERATUR TRANSMITTER MONITOR Doc 70 00 0794A V2 7 20210310 Vector Controls GmbH Switzerland Page 9 10 Subject to change without notice www vectorcontrols com Blank page...

Page 10: ...2 7 20210310 Vector Controls GmbH Switzerland Page 10 10 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls Gmb...

Reviews: