background image

 

MZ3-FU-V01

 

 

Doc: 70-00-0842 V2.2, 20210419 

© Vector Controls GmbH, Switzerland 

Page 2 

Subject to alterations 

www.vectorcontrols.com 

 Technical data  

Power supply 

Operating voltage 

24 V AC/DC ± 10%, 50/60 Hz, Class 2 48 VA max 

Power consumption 

Max. 1,0 VA 

Power backup for real time clock 

Super cap, keeps clock running for 24 h without 
power 

Electrical 

connection

 

Terminal connectors,  
wire 0,34-2,5 mm

2

 

(AWG 22…13)

 

Signal outputs 

Analog outputs 

Output signal 

Maximum load 

 

DC 0...10 VDC 

2 mA or 5 

kΩ

 

Environment 

Operation 

Climatic conditions 

Temperature 
Humidity 

To IEC 721-3-3 

class 3K5 

0...50 ° C (32...122 ° F) 
< 95% RH non-condensing 

Transport & storage 

Climatic conditions 

Temperature 
Humidity 

Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 

class 3K3 and class 1K3 

-

25…70 °C (

-

13…158 °F)

 

< 95% RH non-condensing 

class 2MT2 

Standards 

Degree of protection 

Wall mounted:  

IP40 acc. EN 60529 

Not installed:  

IP00 acc. EN 60529 

Safety class 

III (IEC 60536) 

General 

Housing material: 

Fireproof ABS+PC plastic (UL94 class V-0) 

 

Dimensions (H x W x D)  

including packaging 

145 x 105 x 70 mm (5,7

” x 

4,1

” x 

2.8

”) 

 

 

Weight (incl. packaging) 

155 g (5.5 oz) 

Dimensions mm (in) 

The MZ3-FU-V01 is so designed that it can be incorporated into a commercially available flush box (Frame and mounting 

plate are included). 

 

Selecting the signal from 0-10 VDC to 2-10 VDC with JP1 

 

If JP1 is in position 1-

2, the output signal is 0…10 VDC

 

If JP1 is in position 2-

3, the output signal is 2…10 VDC

 

Parameter copy 

It is now possible to copy settings to an accessory (AEC-PM2) and to copy them 

back to other MZ3. For this, remove the front panel of the MZ3, insert AEC-PM2 in 

the designated plug. Connect OPA-S and copy parameter from MZ3 to AEC-PM2 by 

setting OP06 to 1. 

AEC-

PM2 “Data” LED is ON for 5 seconds after successful parameter copy and 

OP06 is set to 0. If the parameter copy failed the LED blinks for 5 seconds and 

OP06 is set to 7. 

 

Copy parameter from AEC-

PM2 to MZ3 simply by pressing the “Copy” button on 

the AEC-PM2. AEC-

PM2 “Data” LED is ON for 5 seconds after successful parameter 

copy. If the parameter copy failed the LED blinks for 5 seconds. 