MZ3-FU-V01
Doc: 70-00-0842A V2.5, 20230220
© Vector Controls GmbH, Switzerland
Page 5-6
Subject to alternation
www.vectorcontrols.com
Configuration
Configuration of the output signal and jumper
−
If JP1 is in position 1-
2, the output signal is 0…10 VDC
−
If JP1 is in position 2-
3, the output signal is 2…10 VDC
The jumper position can be seen in section "View of rear part, without front panel" page 3.
Output configuration (AO)
Parameter Description
Range
Default
OP00
Output level 0 (MIN): 0…100 % = 0…10.0 VDC
0…100%
0% =
0 V (
JP1 = 1-2
)
2 V (
JP1 = 2-3
)
OP01
Output level 1 (MID): 0…100 % = 0…10.0 VDC
Note: setting a level to 0 disables it
0…100%
50% =
5 V (
JP1 = 1-2
)
6 V (
JP1 = 2-3
)
OP02
Output level 2 (MAX): 0…100 % = 0…10.0 VDC
Note: setting a level to 0 disables it
0…100%
100% =
10 V (
JP1 = 1-2
)
10 V (
JP1 = 2-3
)
OP03
Automatic reset time of the lowest level to the level defined
in OP05. The reset is deactivated with setting = 0
0…255 min
0 min
(deactivated)
OP04
Automatic reset time of the highest level to the level defined
in OP05. The reset is deactivated with setting = 0
0…255 min
0 min
(deactivated)
OP05
Level after automatic reset. This level will be activated once
the reset time defined in OP04 has expired.
0…2
1
OP06
- 0: Parameter copy successful; No action
- 1: Start parameter copy to AEC-PM2
- 7: Copy fail (no AEC-PM2 or communication error)
0…1
7: display only
0
Setting the parameters
The MZ3 is designed to work for most comfort ventilation applications. It is
however possible to fine tune it to fit perfect into the application at hand.
The parameters can be changed during operation through an operation unit
called OPA-S. The operating unit OPA-S must be connected for the
adjustment of the parameters with the MZ3.
Carefully lift the front panel of the MZ3 and pull it away to the front. Plug the
connecting cable of the OPA-S operating unit into the rear part of the MZ3.
Important
The MZ3 does not accept the new settings until the OPA-S parameter menu is exited. The connection must not be
disconnected earlier than five seconds after the last keystroke!
Copy parameters
It is now possible to copy settings to an accessory (AEC-PM2) and to copy them back to
other MZ3. For this, remove the front panel of the MZ3, insert AEC-PM2 in the
designated plug.
Copy parameters from MZ3 to AEC-PM2
Connect OPA-S and copy parameters from MZ3 to AEC-PM2 by setting OP06 to 1. The
"Data" LED of the AEC-PM2 lights up for 5 seconds after successful parameter copying
and OP06 is set to 0. If parameter copying has failed, the LED flashes for 5 seconds and
OP06 is set to 7.
Copy parameters from AEC-PM2 to MZ3
Copy the parameters from AEC-PM2 to MZ3 simply by pressing the "Copy" button on the
AEC-PM2. The "Data" LED on the AEC-PM2 will light for 5 seconds after the parameters
have been successfully copied. If the parameter copy failed, the LED will blink for 5
seconds.