Technical Data 

Power supply 

Operating voltage 

24 V AC/DC ± 10%, 50/60 Hz, Class 2 48 VA max. 

Power consumption 

Max. 1 VA 

Electrical connection

 

Terminal connectors,  

wire 0,34-

2,5 mm2 (AWG 22…13)

 

Signal output

 

Analog output 

Output signal 

Maximum load 

 

DC 0…10 V

 

2 mA or 5 

kΩ

 

Environment

 

Operation 
Climatic conditions 

Temperature 

Humidity 

To IEC 721-3-3 
class 3K5 

0...50 ° C (32...122 ° F) 

< 95% RH non-condensing 

Transport & storage 

Climatic conditions 

Temperature 

Humidity 

Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 

class 3K3 and class 1K3 

-

25…70 °C (

-

13…158 °F)

 

< 95% RH non-condensing 

class 2MT2 

Standards

 

Degree of protection 

Wall mounted:  

IP40 acc. EN 60529 

Not installed:  

IP00 acc. EN 60529 

Safety class 

III (IEC 60536) 

General 

Housing material: 

Flame retardant PC+ABS plastic (UL94 class V-0) 

 

Dimensions (H x W x D)  

including packaging 

145 x 105 x 70 mm (5

,7” x 4,

1

” x 

2,8

”) 

 

 

Weight (incl. packaging) 

155 g (5.5 oz) 

 

Product testing and certification 

 

Declaration of 

Conformity 

Information on the conformity of our products can be found on our website 

www.vectorcontrols.com

 on the corresponding product page under "Downloads". 

 

Connection diagram 

 

 

 

 

 

Description:  

1  GND 

Power supply: 

0 V, -24 VDC, internally connected to signal common 

2  V+ 

Power supply: 

24 VAC, +24 VDC 

3   

Not used, do not connect   

4  AO 

Analog output ventilation:  0/2

…10 VDC

 

 

Mounting instruction 

 

For more information on mounting, refer to MZ3-FU-V01 Installation Manual No. 70-000841 

(

www.vectorcontrols.com

). 

 