background image

 

TCI-W13, TCI-W23 Universal Controller 

A

UX 

F

UNCTIONS 

C

ONFIGURATION

 

 

Doc: 70-00-0365C, V2.0, 20220523  

© Vector Controls GmbH, Switzerland  

Page 20-22 

Subject to alteration 

Heating/cooling mode changeover 

Parameter  Description 

Range 

Default 

Fu 20 

Select heat/cool changeover input (0=function disabled):  

1= 1T,  2= 1H,  3= 1U,  4= 2T,  5= h/c status loop 1,   

6= h/c status loop 2 

0

Fu 21 

Cooling activation delay (seconds)  

0

1275s 

300 

Fu 22 

Input limit 1 

per input 

20 

Fu 23 

Input limit 2 

per input 

40 

 

 

Switch heating/cooling state based on a universal input value. The input may be from a supply media (air or water) 

or outdoor air temperature sensor. For supply media temperature we recommend switching to cooling at 16°C/61°F 

and to heating at 28°C/83°F. For outdoor temperature we recommend switching to cooling at 28°C/83°F and to 

heating at 16°C/61°F outdoor temperature. These recommendations are given as suggestions. The ideal settings may 

be different on the actual project depending on climatic and system conditions.   

 

 

The change between heating and cooling is delayed to avoid unnecessary switching (FU21). Heat/cool status of one 
control loop may also be determined by the heat/cool state of the other loop (FU20= 5 or 6). The control loop used to 

determine the heat /cool state must be set to demand-based heating and cooling with (L23). Set limit 1 and limit 2 to 

switch between heating and cooling with options below. Example: When Limit 2 is greater than Limit 1, switch heat to 

cool at Limit 1, cool to heat at Limit 2. For binary open/close contact, open is a high value (100%), closed is a low 

value (0%).

 

 

 

 

 

Cool 

Mode 

Mode 

Heat 

Input  

Limit 2 > Limit 1  

Heat 

Cool 

Input 

Limit 1 > Limit 2  

Limit 

Limit 

Limit 

Limit 

Summary of Contents for 40-10 0259

Page 1: ...8 time schedules 1 internal temperature sensor 1 universal input 1 passive input 1 binary PWM output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as required...

Page 2: ...ity Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 2...

Page 3: ...puts Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper TI Passive input NTC 10 k 25 C 77 F or open contact AO Analo...

Page 4: ...other heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is les...

Page 5: ...Text OFF displayed with current time W23 temperature W13 Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W23 SCHEDULE...

Page 6: ...each for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or lar...

Page 7: ...EL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W13 Press OPTION 2 sec SEL and H C is displayed Press UP unti...

Page 8: ...from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun Whil...

Page 9: ...t configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneous...

Page 10: ...N UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H 3...

Page 11: ...U00 Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value o...

Page 12: ...setpoints There are two possibilities to change the setpoint in Unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling U...

Page 13: ...that the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equals...

Page 14: ...changeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16 2...

Page 15: ...be individually selected Multiple alarms can be signed to one output If one alarm is selected to simultaneously activate and deactivate an output the one to de activate has precedence With manual pos...

Page 16: ...5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0activates 0 deactivates 0 1650s 0s 1d 06 Choose alarm t...

Page 17: ...larm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be simultaneously selected to activate...

Page 18: ...lay seconds 1275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to...

Page 19: ...n limit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF...

Page 20: ...temperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the ac...

Page 21: ...TCI W13 TCI W23 Universal Controller Doc 70 00 0365C V2 0 20220523 Vector Controls GmbH Switzerland Page 21 22 Subject to alteration Empty page...

Page 22: ...70 00 0365C V2 0 20220523 Vector Controls GmbH Switzerland Page 22 22 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info v...

Reviews: