Technical specifications
WARNING!
This device is intended to be used for comfort applications. Where a device failure endangers human life and/or
property, it is the responsibility of the owner, designer and installer to add additional safety devices to prevent or
detect a system failure caused by such a device failure. The manufacturer of this device cannot be held liable for
any damage caused by such a failure.
Ignoring specifications and local regulations may endanger life, cause equipment damage and void warranty.
Power Supply
Power Requirements
24 VAC ±10%, 50/60 Hz, Class 2, 2.0 A, 48 VA max.
24 VDC ±10%
Power Consumption
Max. 3 VA
Electrical Connection
Terminal Connectors
0.34…2.5 mm
2
wire (AWG 24…12)
Clock backup
Min. 48 hours
Signal inputs
Universal Input
Input Signal
Resolution
Impedance
Setting for Voltage or Current
0
–
10 V or 0
–
20 mA
9.76 mV or 0.019 mA (10 bit)
Voltage: 98kΩ
Current: 240Ω
Universal Input
Range
Accuracy
Input configured to remote temperature (RT) or digital input (DI)
NTC (Sxx-Tn10 sensor): -
40…140
°C (-
40…284 °F)
-
40…0 °C (
-
40…32 °F): 0.5 K
0…50 °C (32…122 °F): 0.2 K
50…100 °C (122…212 °F): 0.5 K
> 100 °C (> 212 °F): 1 K
Humidity Sensor AES3-HT-Ax:
Range
Measuring Accuracy
Hysteresis
Repeatability
Stability
Capacity sensor
0…100 % rH
See Figure to the right
1%
0.1%
< 0.5% / year
Signal outputs
Analog Output
Output Signal
Resolution
Maximum Load
DC 0
–
10 V / 0
–
20 mA
9.76 mV / 0.019 mA
Voltage:
≥
1kΩ
Current:
≤
250
Ω
Relays Outputs
AC Voltage
DC Voltage
0…
48 VAC, 2(1.2)A max. (Observe local regulation)
0…30 VDC, 2A max.
Insulation strength
between relays contacts and system
electronics:
between neighboring contacts:
2000V AC to EN 60 730-1
1250V AC to EN 60 730-1
Environment
Operation
Climatic Conditions
Temperature
Humidity
To IEC 721-3-3
class 3 K5
0…50 °C (32…122 °F)
<95 % RH non-condensing
Transport & Storage
Climatic Conditions
Temperature
Humidity
Mechanical Conditions
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-25
…7
0 °C (-13
…158 °F)
<95 % RH non-condensing
class 2M2
Standards
Degree of Protection
IP30 to EN 60 529
Pollution Class
II (EN 60 730-1)
Safety Class
III (IEC 60536)
Overvoltage Category
I (EN 60 730-1)
General
Material:
Cover, back part
Mounting Plate
Fire proof ABS plastic (UL94 class V-0)
Aluminum
Dimension (H x W x D)
Front part: 21 x 88 x 88mm (0.8 x 3.5 x 3.5 in.)
Power case: ø 58 x 32 mm (ø 2.3” x 1.3”)
Weight (including package)
TCI-W13
TCI-W23
205g (7.2 oz.)
220g (7.8 oz)
Product testing and certification
Declaration of conformity
Information about the conformity of our products can be found on our website
www.vectorcontrols.com on the corresponding product page under "Downloads"
Figure 1: Max RH-tolerance at 25°C (77°F)
per sensor type
Relative humidity accuracy
%RH
%RH
10 20 30 40
100
90
0
50 60 70 80
±1
±0
±2
±3
±4
±5
AES3-HT-A2
AES3-HT-A3
AES3-HT-A5