TLC3-FCR-T Engineering Manual

 

 

Doc: 70-00-0200, V3.1 Date: 20160411 

© Vector Controls GmbH, Switzerland 

Page 1 

Subject to alteration 

TLC3-FCR-T  
Intelligent Fan Coil controller 

Features 

 

The PWM control option reduces room temperature 

fluctuations and energy consumption 

 

Low power energy consumption: < 1W per unit 

 

Temperature control for 2- pipe fan coil systems.  

 

External sensor or open contact for remote control,  

external heat – cool change or auto-changeover on supply 

temperature with selectable activation limits 

 

Automatic fan control for three stage fans.  

 

Cost saving option with Economy functionality and set point 

limitations 

 

Control for single stage heating, cooling and fan only 

operation modes 

 

Password protected programmable user and control 

parameters 

o

 

Setpoint range limitation 

o

 

Access control for setpoints, fan speeds and mode change 

o

 

Access control for heat/cool change and time programs 

o

 

Select your display contents 

o

 

Selectable behavior after return from power failure 

 

Temperature display in Celsius or Fahrenheit 

Deluxe Version: 

 

Clock and time schedule functions with power failure protection 

 

Blue backlight for LCD 

 

Infrared remote controller option:  

With special features for Boost and delayed switching on or off 

Applications 

 

Air Only Systems:  

o

 

Constant Air Volume systems with three stage fans for single or dual duct systems 

 

Air/Water Systems:  

o

 

Fan Coil units for 2-pipe systems  

o

 

radiator control, chilled ceiling 

 

Simple individual room control for hotel rooms, meeting rooms, etc.  

 

PWM or On-Off-Control of 2 spring return valves or 3-point on-off or floating control of one 3-point valve.  

General Description 

The TLC3-FCR-T is a stand-alone electronic fan coil controller with one control loop. The TLC3-FCR-T features 1 NTC 

temperature sensor input, 1 external NTC or open contact input and four binary outputs (Relays).  
A detailed parameterization is possible with the use of a simple configuration routine. The TLC3-FCR-T can be 

configured using the standard operation terminal. No special tools or software is required.  

Ordering 

Item Name 

Item code 

Variant 

Power 

Features 

TLC3-FCR-T 

TLC3-FCR-T-W01 

40-10 0129 

40-10 0129-01 

Standard 

Cooling only 

24VAC/DC 

Fan coil controller with:  
1 TI int or ext  

3 DO (Relay) Fan control 

1 DO (Relay) Binary valve control 

TLC3-FCR-T-230 

TLC3-FCR-T-230-W01 

40-10 0114 

40-10 0114-01 

Standard 

Cooling only 

230VAC 

TLC3-FCR-T-D-24 

TLC3-FCR-T-D-24-W01 

40-10 0134 
40-10 0134-01 

Deluxe 

Cooling only 

24VAC/DC 

TLC3-FCR-T-D-230 

TLC3-FCR-T-D-230-W01 

40-10 0115 
40-10 0115-01 

Deluxe 

Cooling only 

230VAC 

Selection of actuators, fans and sensors 

Temperature Sensors: Use only our approved NTC sensors to achieve maximum accuracy.  Recommended is SDB-

Tn10-15 as Duct sensor, SRA-Tn10 as Room sensor and SDB-Tn10-15+AMI-10 as immersion sensor.  
Binary auxiliary devices: E.g. fans, on/off valves, etc.  Do not directly connect devices that exceed switching power. 
Observe startup current on inductive loads! Do not connect more than one fan coil unit to one controller. 

Summary of Contents for 40-10 0114

Page 1: ...tems o radiator control chilled ceiling Simple individual room control for hotel rooms meeting rooms etc PWM or On Off Control of 2 spring return valves or 3 point on off or floating control of one 3...

Page 2: ...721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards...

Page 3: ...at the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the intercon...

Page 4: ...ft once the temperature reaches 10 C 50 F Frost protection display will remain until a button is pressed Frost protection can be enabled disabled using user parameter UP 09 Toggle C F display with one...

Page 5: ...ess UP DOWN to step through available options d1 7 d1 6 d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7...

Page 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be...

Page 7: ...ontrol of fan speeds ON OFF ON Enabled UP 03 Function of advanced mode long press right key 0 disabled 1 access to heat cool fan only change 2 access to clock settings and time programs 3 access to he...

Page 8: ...rence between switching on and switching off A small hysteresis will increase the number of switching cycles and thus the wear on fan and relays contacts 0 10 0 C 20 0 F 0 5 C 1 F FC 08 Mold Protectio...

Page 9: ...verridden by using the terminal Connecting the input to signal common returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy FC16 4...

Page 10: ...TLC3 FCR T Engineering Manual Doc 70 00 0200 V3 1 Date 20160411 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes...